CCLME.ORG - DIVISION 1. STATE FIRE MARSHAL
Loading (50 kb)...'
(continued)


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 574.6. Recordkeeping.
(a) Personnel making inspections shall keep records of all fire extinguishers inspected, including those extinguishers that were found to require corrective actions.
(b) At least monthly, the date the inspection was performed and the initials of the person performing the inspection shall be recorded on a tag or label attached to the fire extinguisher, or an inspection checklist maintained on file, or an electronic system (e.g. bar coding) that provides a permanent record.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575. Servicing, General.
Servicing which includes maintenance, recharging and hydrostatic testing shall be performed by concerns licensed by the State Fire Marshal having available the appropriate servicing manual(s), the proper types of tools, recharging agents and materials, lubricants, and manufacturer's recommended replacement parts or parts of equal quality. Maintenance, recharging and hydrostatic testing shall be done in accordance with the appropriate manufacturer's service manual(s) and the requirements of this chapter.





s 575.1. Maintenance and Required Service Intervals.
(a) Fire extinguishers shall be subjected to maintenance annually as described in this chapter or immediately after use or when specifically indicated by an inspection or at the time of hydrostatic test. For purposes of maintenance, hydrostatic tests required during the same calendar year shall be performed at the time of the annual maintenance or recharge.
(b) Nonrechargeable fire extinguishers shall not be recharged or hydrostatically tested but shall be discharged and removed from service at a maximum interval of 12 years from the date of manufacture.
Exception: Nonrechargeable fire extinguishers containing a halon agent shall be removed from service, not discharged, and returned to the manufacturer or fire extinguisher distributor having the capability of recovering the halon agent.
(c) When additional fire extinguishers are installed in excess of those required, the additional extinguishers shall be subjected to maintenance and hydrostatically tested in the same manner and at intervals as set forth in this chapter for required extinguishers.
(d) New fire extinguishers that are fully charged by the manufacturer shall, after being sold, be subjected to maintenance within one year from the date of manufacture in accordance with this chapter. If only the year is shown, the new extinguisher shall be due for maintenance by January 1st of the year following the year of manufacture in accordance with this chapter.
Exception: A licensed fire extinguisher concern may attach the tag described in Section 596.1(a) and punch the new extinguisher block and date the extinguisher was sold. Extinguishers tagged in this manner shall be subjected to maintenance one year from the date on the tag in accordance with this chapter. Extinguishers more than two years old from date of manufacture shall not be tagged as new extinguishers.
(e) At the time of installation and at each annual maintenance, extinguishers shall be placed in a fully charged and operable condition free from defects which may cause malfunctions.
(f) At the time of service, hydrostatic testing, or at any time when parts are replaced, an itemized invoice showing work performed and parts replaced shall be provided by the licensee to the owner or possessor of the fire extinguisher.
(g) The licensee shall offer to return all replaced parts to the portable fire extinguisher owner or owner's representative, except such parts as the licensee is required to return to the manufacturer of the portable fire extinguisher under any warranty arrangement.
(h) Annual maintenance or recharging shall not be performed more than 30 days before the date the maintenance, service or recharge is due. This section shall not rule out the maintenance required by Section 575.1(a).


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160, 13162, 13177 and 13190.3, Health and Safety Code.






s 575.2. Maintenance Requirements.
(a) The procedures outlined in this chapter are common to most fire extinguishers and shall be performed at each annual maintenance, in addition to the manufacturer's instruction or other requirements of this chapter. All contents shall be emptied from the extinguisher, except as provided herein in this chapter.
(b) Mechanical Parts.
Any parts needed for replacement shall be the manufacturer's recommended replacement parts or parts of equal quality. Parts not designated as the manufacturer's recommended replacement parts shall be proven by a recognized testing laboratory to be of equal quality.
(c) If the source of leakage cannot be corrected by parts replacement, extinguishers shall be removed from service in accordance with Section 577.1 of this chapter.


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160, 13177 and 13190.3, Health and Safety Code.






s 575.3. Maintenance Procedures.
(a) Maintenance procedures shall include a thorough examination of the three basic elements of an extinguisher:
(1) mechanical parts
(2) extinguishing agent
(3) expelling means

Exception: During annual maintenance, it is not necessary to internally examine nonrechargeable fire extinguishers, carbon dioxide fire extinguishers, stored pressure dry chemical or dry powder fire extinguishers that require a 12 year hydrostatic test, halogenated agent fire extinguishers, wet chemical fire extinguishers or AFFF/FFFP fire extinguishers that use a pre-mixed charge. However, such extinguishers shall be thoroughly examined externally in accordance with the applicable items of 575.3(a)(1) and Table 4.
For Stored Pressure Dry Chemical and Dry Powder Fire Extinguishers, see Section 575.4
For Carbon Dioxide Fire Extinguishers, see Section 575.5
For Stored Pressure Halogenated Agent Fire Extinguishers, see Section 575.6
For Stored Pressure Water Type Fire Extinguishers, see Section 575.7
For AFFF and FFFP Fire Extinguishers that use a pre-mixed charge, see Section 575.8.
For Stored Pressure Wet Chemical Fire Extinguishers, see Section 575.16.
(b) Fire extinguishers shall be thoroughly examined externally and the appropriate corrective action performed in accordance with the applicable items of Table 4, External Examination Maintenance Checkpoints.
(c) Fire extinguishers shall be weighed on accurate scales and it shall be verified that the total weight is within the allowable tolerances specified by the manufacturer.
Exception: Water-type and wet chemical fire extinguishers that have the liquid amount specified on the extinguisher shell, a fill level mark or an anti-overfill tube.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






Table 4
External Examination Maintenance Checkpoints




Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.4. Dry Chemical and Dry Powder Portable Fire Extinguishers.
(a) Stored Pressure Extinguishers
(1) Every 6 years stored pressure dry chemical and dry powder fire extinguishers that require a 12 year hydrostatic test shall be discharged, emptied and subjected to the applicable maintenance procedures as specified by the manufacture's requirements.
(2) Stored pressure dry chemical and dry powder extinguishers shall be fully discharged to check the operation of the discharge valve and pressure gauge.

(3) The dry chemical agent may be reused provided an approved closed recovery system is used and the agent is stored in a sealed container to prevent contamination.
(4) Prior to reuse, the dry chemical or dry powder agent shall be thoroughly checked to insure:
(A) Appropriate type agent.
(B) Agent is not contaminated.
(C) Agent is in a free flowing powdery condition.
(5) Where doubt exists with respect to the type, contamination, or condition of the dry chemical or dry powder agent, the agent shall be discarded.
(b) Cartridge and Cylinder Operated Extinguishers.
(1) At the time of annual maintenance, cartridge and cylinder operated dry chemical and dry powder fire extinguishers shall be emptied.

(2) Prior to reuse, the dry chemical or dry powder agent shall be thoroughly checked to insure:
(A) Appropriate type agent.
(B) Agent is not contaminated.
(C) Agent is in a free flowing powdery condition.
(3) Where doubt exists with respect to the type, contamination, or condition of the dry chemical or dry powder agent, the agent shall be discarded.
(4) Cartridges of cartridge operated portable fire extinguishers shall be replaced when the loss of weight as compared with the original weight as stamped on the cartridge is equal to or more than that as permitted in instructions on the label.
(5) Cartridges of every cartridge-operated extinguisher shall be weighed annually. The minimum graduation for the scale shall not be larger than 1/100 of the cartridge being weighed and shall be accurate to plus or minus one scale graduation. Scales used in commercial applications (legal for trade) shall comply with Sections 12500(a) and 12501.1, of the California Business and Professions Code and Section 4000, Title 4, of the California Code of Regulations. Straight faced spring scales (i.e. fish scales) shall not be used.
(6) Replacement cartridges for cartridge operated extinguishers shall conform to the manufacturer's requirements.
(7) Cylinders of wheeled cylinder operated dry chemical extinguishers shall maintain a pressure of not less than 1,500 P.S.I. Wheeled pressurized dry chemical extinguishers shall maintain proper expelling pressure as indicated on the pressure gauge.
(c) Multipurpose dry chemicals shall not be mixed with alkaline-based dry chemicals.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160 and 13177, Health and Safety Code.






s 575.5. Carbon Dioxide Extinguishers.
Internal maintenance of carbon dioxide extinguishers shall be performed every 5 years at the time of hydrostatic test. The components shall be replaced in accordance with the manufacturer's recommendations.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.6. Halogenated Agent Extinguishers.
(a) Every 6 years, stored pressure halogenated fire extinguishers that require a 12-year hydrostatic test shall be emptied and subjected to the maintenance procedures as required by Article 6.
(b) The removal of Halon 1211 from fire extinguishers shall only be done using a halon closed recovery system in compliance with the 1997 3rd Edition of the UL Standard 2006, Standard for Halon 1211 Recovery/Recharge Equipment. The removal of agent from other halogenated agent fire extinguishers shall only be done using a closed recovery system.
(c) The extinguisher cylinder shall be examined internally for contamination and/or corrosion. The halogenated agent retained in the system recovery cylinder shall only be used if no evidence of internal contamination is observed in the extinguisher cylinder. Halogenated agent removed from extinguishers that contain evidence of internal contamination or corrosion shall be processed in accordance with the manufacturer's instruction.
(d) When the applicable maintenance procedures are performed during periodic recharging or hydrostatic testing, the 6-year requirement shall begin from that date of the recharging or testing.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.7. Stored Pressure Water Type Extinguishers.
Stored pressure extinguishers containing a water or loaded stream agent shall be disassembled on an annual basis and subjected to a complete maintenance in accordance with Section 575.3. Prior to disassembly, the extinguisher shall be fully discharged to check the operation of the discharge valve and pressure gauge.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.8. AFFF and FFFP Extinguishers.
AFFF and FFFP fire extinguishers shall be maintained in accordance with the following:
(a) Pre-Mix: Extinguisher shall be externally examined annually, and broken down and the agent replaced every three years.
(b) Solid Type:
(1) Cartridge shall be removed and the extinguisher serviced in accordance with Section 575.3, and the cartridge re-installed.
(2) Cartridges shall be replaced with a new one every five years.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.9. Pump-Tank Extinguishers.
Every 12 months, pump-tank water and pump-tank calcium chloride base antifreeze types of extinguishers shall be recharged with new chemicals or water, as applicable.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.10. Out of Service.
Fire extinguishers removed from service for maintenance or recharge shall be replaced by fire extinguishers suitable for the type of hazard protected and shall be of at least equal rating.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.11. Safety Pins.
Upon completion of annual maintenance, an extinguisher shall have installed a safety pin compatible with the valve required by the ANSI/UL standards contained in 561.2. The safety pin shall be held in place with a seal as specified in Section 575.12.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160, 13162 and 13177, Health and Safety Code.








s 575.12. Seals or Tamper Indicators.
(a) A tamper seal or tamper indicator shall be provided on every portable fire extinguisher. Tamper seals shall be component recognized by an approved testing laboratory for use on fire extinguishers or be the manufacturer's approved replacement.
(b) At the time of maintenance, the tamper seal of rechargeable fire extinguishers shall be removed by operating the pull pin or locking device. After the applicable maintenance procedures are completed, a new tamper seal shall be installed.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160 and 13162, Health and Safety Code.






s 575.13. Anti-Freeze Solution.
Anti-freeze solution for anti-freeze extinguishers shall be put through a fine strainer prior to placing it into the extinguisher so as to prevent any possibility of undissolved salts impairing the normal function of the extinguisher.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160, Health and Safety Code.








s 575.14. Nitrogen Cylinder Operated Wheeled Extinguishers.
Pressure regulators and nitrogen cylinders on wheeled fire extinguishers shall be maintained in accordance with manufacturer's instructions.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160 and 13177, Health and Safety Code.






s 575.15. Conductivity Test.
(a) An annual conductivity test shall be conducted on all carbon dioxide hose assemblies. Hose assemblies found to be nonconductive shall be replaced.
(b) Carbon dioxide hose assemblies that pass a conductivity test shall have the test information recorded on a suitable metallic label or equally durable material that has a minimum size of 1/2 in. x 3 in. (1.3 cm x 7.6 cm). The label shall be affixed to the hose by means of a heatless process. The label shall include the following information:

(1) Month and year the test was performed, indicated by perforation, such as is done by a hand punch.
(2) Initials and EE# of person performing the test.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 575.16. Wet Chemical Fire Extinguishers.
Internal maintenance of wet chemical fire extinguishers shall be performed every 5 years at the time of hydrostatic test in accordance with the manufacturer's recommendations.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 576.1. Maintenance Recordkeeping.
Upon completion of the maintenance procedures prescribed by Section 575.3, each portable fire extinguisher shall be fitted with an annual maintenance tag as prescribed in Article 9.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160, 13162 and 13177, Health and Safety Code.






s 577.1. Condemned Extinguishers.
(a) Portable fire extinguishers shall not be repaired except as permitted by manufacturer's instructions using manufacturer's recommended replacement parts or parts of equal quality. Portable fire extinguishers shall not be converted from one type or class to another type or class of extinguisher.
(b) Portable fire extinguishers which have been repaired, converted or altered in conflict with Section 575.2(c) are prohibited from use as portable fire extinguishers. Such extinguishers shall be removed from service and tagged with a red tag bearing the term "Condemned" on each face.
Exception : The exchange of defective or broken parts with approved parts as defined in Section 557.16(b) or equipment or materials listed as defined in Section 557.12(c) shall not be construed asThe exchange of defective or broken parts with approved parts as defined in Section 557.16(b) or equipment or materials listed as defined in Section 557.12(c) shall not be construed as "repair".
(c) Condemned portable fire extinguishers shall be destroyed by the owner or at the owner's direction.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Sections 13160, 13162 and 13177, Health and Safety Code.






s 577.2. Obsolete Fire Extinguishers.
The following types of fire extinguishers are considered obsolete and shall be removed from service:
(1) Soda acid types
(2) Chemical foam (excluding AFFF and FFFP)
(3) Vaporizing liquid (e.g., carbon tetrachloride)
(4) Cartridge-operated water
(5) Cartridge-operated loaded stream
(6) Copper or brass shell fire extinguishers (excluding pump tanks) joined by soft solder or rivets
(7) Stored pressure water extinguishers with fiberglass shells


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.1. Recharging, General:
(a) All rechargeable type extinguishers shall be recharged after use or as indicated by an inspection or when performing maintenance.
(b) When performing the recharging, the recommendations of the manufacturers shall be followed. For recharge chemicals, see Section 578.2.
(c) The amount of recharge agent shall be verified by weighing on an accurate scale. The total weight shall be within the allowable tolerances specified by the manufacturer.
Exception : Water-type and wet chemical fire extinguishers that have the liquid amount specified on the extinguisher shell, a fill level mark or an anti-overfill tube.Water-type and wet chemical fire extinguishers that have the liquid amount specified on the extinguisher shell, a fill level mark or an anti-overfill tube.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.2. Recharge Agents.
Only those agents specified on the nameplate, or agents proven to have equal chemical composition, physical characteristics and fire extinguishing capabilities shall be used. Agents listed specifically for use with the fire extinguisher shall be considered to comply with the requirements of this section.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.3. Dry Powder.
Pails or drums containing dry powder agents for scoop or shovel application for use on metal fires shall be kept full and covered at all times. The dry powder shall be replaced if found damp.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.4. Replacement Pressure Gauge.
Replacement pressure gauges shall have the proper indicated charging (service) pressure, be marked for use with the agent in the extinguisher and be compatible with the extinguisher valve body material.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.5. Precautionary Pressurization Measures.
A rechargeable stored pressure type extinguisher shall be pressurized only to the charging pressure specified on the extinguisher nameplate. A regulated source of pressure, set no higher than 25 psi (172 kPa) above the operating (service) pressure, shall be used to pressurize fire extinguishers. An unregulated source of pressure, such as a nitrogen cylinder without a pressure regulator, shall never be used because the fire extinguisher could be over-pressurized and possibly rupture. A fire extinguisher shall never be left connected to the regulator of a high-pressure source for an extended period of time. A defective regulator could cause the container to rupture due to excess pressure.
(b) The gauge used to set the regulated source of pressure shall be calibrated at least annually.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.6. Pressurizing Gas.
Only standard industrial grade nitrogen with a dew point of -60o F (-51o C) or lower (CGA nitrogen specification G10.1, grades D through P) shall be used to pressurize stored pressure dry chemical, dry powder and Halon type fire extinguishers. Compressed air through moisture traps shall not be used for pressurizing even though so stated in the instructions on older fire extinguishers.
E XCEPTION N o. 1: Compressed air may be used from special compressor systems capable of delivering air with a dew point of -60 <> F (-51.1 <> C) or lower. The special compressor system shall be equipped with an automatic monitoring and alarm system to ensure that the dew point remains at or below -60 <> F (-51.1 <> C) at all times. E XCEPTION N o. 2: Some fire extinguishers are required to be pressurized with argon. They shall be repressurized only with the type of expellant gas referred to on the fire extinguisher label.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.7. Conversion of Extinguisher Types.
No extinguisher shall be converted from one type to another, nor shall any extinguisher be converted to use a different type of extinguishing agent.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.8. Removal of Moisture.
For all non-water type of extinguishers any moisture shall be removed before recharging.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.9. Carbon Dioxide Recharging.
The vapor phase of carbon dioxide shall not be less than 99.5 percent carbon dioxide. The water content of the liquid phase shall not be more than 0.01 percent by weight [-30o F (-34.4o C) dew point]. Oil content of the carbon dioxide shall not exceed 10 ppm by weight.
Note: Carbon Dioxide obtained from dry ice converters will generally be unsatisfactory unless it is properly processed to remove excess water and oil. The preferred source of carbon dioxide for recharging extinguishers is from a low-pressure supply, either directly or via dry cylinders used as an intermediary means.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.10. Leak Test.
(a) After charging, a leak test shall be performed on all stored pressure and self-expelling type fire extinguishers. Leak tests shall be performed by following the manufacture's requirements and may include applying a leak test solution or a solution of soapy water.
(b) Leak testing of halogenated agent extinguishers shall not use water. A halogenated gas leak detector shall be used to determine leakage.

Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.11. Recharging Water Types.
When recharging stored pressure extinguishers, overfilling resulting in improper discharge is to be avoided. The proper amount of liquid agent shall be determined by using one of the following:
(a) exact measurement in gallons, or by weight
(b) use of an anti-overfill tube when provided, or
(c) use of a fill mark on extinguisher shell, when provided.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.12. Wet Chemical Agent Re-Use.
Wet chemical agents shall not be re-used. If a wet chemical extinguisher is partially discharged, all remaining wet chemical shall be discarded.


Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 578.13. Recharging Water Types.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 580. Description.







s 581. Unlawful Use.







s 582. Permissive Use.







s 584. Registration Number.







s 585. Designation of Type.







s 586. Cease Use Order.







s 587. Legibility.







s 591. False or Misleading Statements.







s 591.1. Hydrostatic Testing, General.
Hydrostatic testing shall be performed by persons licensed by the State Fire Marshal in pressure testing procedures and safeguards, and having available suitable testing equipment, facilities and appropriate servicing manual(s).


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 591.2. Corrosion.
If, at any time, an extinguisher shows evidence of corrosion or mechanical damage, it shall be hydrostatically tested, subject to the provisions of Section 591.6.
EXCEPTION No. 1: Pump tanks do not require a hydrostatic test.
EXCEPTION No. 2: Extinguishers having nonrefillable disposable containers shall be removed from service in accordance with Section 574.5.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 591.3. Written Certification.
Written approval from the D.O.T. to operate the equipment must be obtained by a licensed portable fire extinguisher concern before performing D.O.T. required hydrostatic tests of cylinders. This written approval shall be available to the State Fire Marshal or authorized representative for inspection.


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160 and 13177, Health and Safety Code.








s 591.4. Restricted Service.
Any portable fire extinguisher requiring a hydrostatic test shall not be serviced until such extinguisher has been subjected to and passed the required hydrostatic test.


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160 and 13177, Health and Safety Code.






s 591.5. Replacement Extinguishers.
Portable fire extinguishers shall not be removed from the premises for hydrostatic testing or any other purpose, without first replacing the extinguisher with a comparable unit.


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160, 13162 and 13177, Health and Safety Code.






s 591.6. Examination of Cylinder Condition.
When an extinguisher cylinder or shell has one or more conditions listed in this section, it shall be destroyed by the owner or at the owner's direction:
(a) When there exists repairs by soldering, welding, brazing, or use of patching compounds.
Note: For welding or brazing on mild steel shells, consult the manufacturer of the extinguisher.
(b) When the cylinder or shell threads are damaged.
(c) When there exists corrosion that has caused pitting, including under removable nameplate band assemblies.
(d) When the extinguisher has been burned in a fire.
(e) When a calcium chloride type of extinguishing agent was used in a stainless steel extinguisher.
(f) When the shell is of copper or brass construction joined by soft solder or rivets.
(g) All inverting-type extinguishers.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 591.7. Aluminum Shell/Cylinder.
Extinguishers having aluminum cylinders or shells suspected of being exposed to temperatures in excess of 350 degrees F (177 degrees C) shall be removed from service.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 592. Frequency.
At intervals not exceeding those specified in Table 5, extinguishers shall be hydrostatically tested.
EXCEPTION No. 1: Nonrefillable factory-sealed disposable containers do not require hydrostatic testing. (See Section 592.4.)
EXCEPTION No. 2: Extinguishers utilizing a cylinder that has been manufactured to D.O.T. specifications shall be hydrostatically tested, or replaced, according to the requirements of D.O.T.
EXCEPTION No. 3: For extinguishers not covered in Exceptions No. 1 and 2 the first retest may be conducted within 12 months of the specified test intervals.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 592.1. Compressed Gas Cylinders and Cartridges.
Nitrogen cylinders or cartridges used for inert gas storage used as an expellant for wheeled extinguishers shall be hydrostatically tested every five years.
Exception: Cylinders (except those charged with carbon dioxide) complying with Part 173.34(e) 15, Title 49, Code of Federal Regulations, shall be hydrostatically tested every 10 years.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 592.2. Hose Assemblies.
(a) A hydrostatic test shall be performed on extinguisher hose assemblies which are equipped with a shutoff nozzle at the end of the hose. The test interval shall be the same as specified for the extinguisher on which the hose is installed.
(b) Test pressure for hose assemblies shall be as follows:
(1) Carbon Dioxide - 1,250 psi;

(2) Dry Chemical - 300 psi or at service pressure, whichever is higher.
(c) Hose assemblies passing the hydrostatic test shall be thoroughly dried internally. If heat is used, the temperature shall not exceed 150 <> F (66 <> C).


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 592.3. Vehicles.
Extinguishers installed on vehicles shall be hydrostatically tested every five years.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 592.4. Nonrefillable Factory-sealed Disposable Containers.
Nonrefillable factory-sealed disposable containers shall not be reused and shall be disposed of pursuant to the requirements of Section 574.5.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 592.5. Obsolete Fire Extinguishers.


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160 and 13177, Health and Safety Code.






s 592.6. Copper, Brass, or Fiberglass Shells.
Table 5

Hydrostatic Test Interval for Extinguishers
Extinguisher type Test Interval
(Years)
Stored Pressure Water 5
and/or Antifreeze/Loaded Stream
AFFF (Aqueous Film Forming Foam) 5
FFFP (Film Forming Fluoroprotein Foam) 5
Wet Chemical 5
Dry Chemical with Stainless Steel Shells 5
Carbon Dioxide 5
Dry Chemical, Stored Pressure with
Mild Steel Shells, Brazed Brass
Shells, or Aluminum Shells 12
Dry Chemical, Cartridge and Cylinder-Operated,
with Mild Steel Shells 12
Halogenated Agents 12
Dry Powder, stored pressure, cartridge- or cylinder-operated
with mild steel shells 12




Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 593.1. Test Pressures, High Pressure Cylinders.
(a) Carbon dioxide extinguishers shall be tested at 5/3 the service pressure as stamped into the cylinder.
Exception: Carbon dioxide extinguishers having cylinder specification ICC3 shall be tested at 3,000 psi (20 685 kPa).
(b) Nitrogen cylinders and carbon dioxide cylinders used with wheel extinguishers shall be tested at 5/3 the service pressure as stamped into the cylinder.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 593.2. Stored Pressure Types.
All stored pressure types of extinguishers shall be hydrostatically tested at the factory test pressure not to exceed three times the normal operating pressure.
Exception : Extinguishers manufactured to D.O.T. specifications shall be hydrostatically tested according to the requirements of D.O.T.Extinguishers manufactured to D.O.T. specifications shall be hydrostatically tested according to the requirements of D.O.T.

Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 593.3. Cartridge-Operated Types.
Cartridge-cylinder-operated dry chemical and dry powder types of extinguishers shall be hydrostatically tested at their original factory test pressure as shown on the nameplate or shell.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 594.1. Test Equipment and Procedures, General.
When extinguisher shells, cartridges or cylinder fail a hydrostatic pressure test, they shall be destroyed by the owner or at the owner's direction.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 594.2. Test Equipment for D.O.T. Specification Cylinders.
The equipment for testing D.O.T. specification cylinders shall be of the type that meets the specifications of the pamphlet Methods for Hydrostatic Testing of Compressed Gas Cylinders (Pamphlet C-1), published by the Compressed Gas Association.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.








s 594.3. Test Equipment for Low Pressure Non-D.O.T. Specification Cylinders and Hose Assemblies.
(a) The required equipment for testing low pressure non-D.O.T. specification cylinders and hose assemblies consists of the following:
(1) Cylinders and hose assemblies shall be tested within a protective cage device, or placed behind a protective shield, that will permit visual observation while under pressure for leaks, bulges, and other harmful defects.
(2) A hydrostatic test pump, hand or power operated, shall be capable of producing not less than 150 percent of the test pressure. It is to include appropriate check valves and fittings.
(3) A flexible connection between the test pump and the test cylinder shall be provided with necessary fittings to test through the extinguisher nozzle, test bonnet, or hose outlet, as applicable.
(4) licensed individuals and licensed companies performing this service shall maintain a license in conformance with section 595.5(a).


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 594.4. Testing Procedures.
(a) D.O.T. specification cylinders.
(1) In addition to the visual examination required prior to test as stated in Section 591.6, an internal examination shall be made prior to the hydrostatic test. The procedures for this internal examination shall be in accordance with the requirements of the Standard for Visual Inspection of High Pressure Aluminum Compressed Gas Cylinders (CGA C-6.1), published by the Compressed Gas Association.

(2) The hydrostatic testing of D.O.T. specification cylinders shall be in accordance with the procedures specified in the pamphlet Methods for Hydrostatic Testing of Compressed Gas Cylinder (Pamphlet C-1), published by the Compressed Gas Association.
(b) Low Pressure Non-D.O.T. Specification Cylinders.
(1) All valves and internal parts shall be removed and the extinguisher emptied.
Exception: On some dry chemical and dry powder extinguishers (cartridge-operated), the manufacturer recommends that certain internal parts not be removed.
(2) All traces of extinguishing material shall be removed from the inside of dry chemical and dry powder type shells before filling with the test liquid.
(3) The cartridges, and some cartridge receivers of dry chemical and dry powder extinguishers having externally mounted gas cartridges, shall be removed and a suitable plug inserted into the shell opening at the point of removal.

(4) On wheeled extinguishers of the stored-pressure water, loaded stream, or cartridge-operated types, the discharge nozzle shall be removed and the complete remaining assembly, including the hose, then tested as described in Section 592.2.
(5) On all wheeled dry chemical, dry powder, Halon 1211, AFFF/FFFP, and carbon dioxide extinguishers equipped with a shutoff nozzle at the outlet end of the hose, the hose (complete with couplings but without the discharge nozzle) shall be removed and tested separately.
(6) On all wheeled stored pressure dry chemical extinguishers, the head assembly is to be removed and be replaced with a suitable test bonnet.
(7) The hose of the hydrostatic test pump is then attached by the flexible connection to the discharge nozzle, hose assembly, test bonnet, or test fitting, as is applicable. In the case of wheeled dry chemical and dry powder extinguishers, procedures and fittings should be those recommended by the manufacturer.
(8) The test liquid supply to the test pump is to be turned on and the extinguisher then filled to the top of its collar.

(9) For extinguishers tested with their cap in place, the cap must be tightened SLOWLY while the test liquid supply remains open. When all of the entrapped air within the shell has been bled off and after test liquid emerges, the cap must be tightened fully.
(10) For extinguisher tested with a test bonnet or fitting, the bonnet or fitting must be tightened FULLY while the water supply remains open. When all of the entrapped air within the shell has been bled off and after test liquid emerges, the vent must be closed tightly.
(11) Pressure is then applied at a rate-of-pressure rise so the test pressure is reached in not less than 30 seconds. This test pressure is maintained for at least 30 seconds. Observations are made at this time to note any distortion or leakage of the extinguisher shell.
(12) If no distortion or leakage is noted and if the test pressure has not dropped, the pressure on the extinguisher shall be released. The extinguisher is then considered to have passed the hydrostatic test.
(13) All traces of test liquid and moisture must be removed from all dry chemical, dry powder, and halogenated agent extinguishers by use of a cylinder dryer. If a heated air stream is used, the temperature within the shell must not exceed 15 degrees F (66 degrees C).
(14) Any extinguisher shell that fails this hydrostatic test must be destroyed by the owner or at the owner's discretion.
(c) Testing Procedures -Hose Assemblies.
(1) The discharge nozzle must be removed from the hose assembly without removal of any hose couplings.
(2) For dry chemical and dry powder types, all traces of dry chemical or dry powder must be removed.
(3) The hose must be completely filled with test liquid before testing.
(4) Pressure is then applied at a rate-of-pressure rise to reach the test pressure within one minute. The test pressure is to be maintained for one full minute. Observations are then made to note any distortion or leakage.

(5) If no distortion or leakage is noted, or the test pressure has not dropped, or the couplings have not moved, the pressure is then to be released. The hose assembly is then considered to have passed the hydrostatic test.
(6) Hose assemblies passing the test shall be dried internally. If heat is used for drying, the temperature shall not exceed 150 degrees F (66 degrees C).
(7) Hose assemblies failing a hydrostatic test must be destroyed by the owner or at the owner's discretion.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 594.5. Recording of Tests.
(a) High Pressure D.O.T. Specification Cylinders. For high pressure cylinders passing a hydrostatic test, the month and year shall be stamped in accordance with the requirements set forth by D.O.T. Recording (stamping) shall be placed only on the shoulder, top head, neck, or footring (when so provided) of the cylinder.
(b) Low Pressure D.O.T. Cylinders. Extinguisher shells of low pressure D.O.T. cylinders that pass a hydrostatic test shall have the test information provided in accordance with D.OT. requirements and recorded on a suitable metallic label or equally durable material. The label shall be affixed by a heatless process to the shell. These labels shall be self-destructive when removal from an extinguisher shell is attempted. The label shall include the following information:
(1) Month and year the test was performed, indicated by a perforation, such as by a hand punch.
(2) Test pressure used.
(3) Name, address and license number (E#) of the concern.
(4) For D.O.T. Specification cylinders, the D.O.T. Retesters Identification Number (RIN), if applicable.
(5) For D.O.T. Specification cylinders, the letter "S" if the Modified Test Method was used.
(c) Low Pressure (non-D.O.T.) Cylinders. Extinguisher shells of low-pressure non-D.O.T. cylinders that pass a hydrostatic test shall have the test information recorded on a suitable metallic label or equally durable material. The label shall be affixed by a heatless process to the shell. These labels shall be self-destructive when removal from an extinguisher shell is attempted. The label shall include the following information.
(1) Month and year the test was performed, indicated by a perforation, such as by a hand punch.
(2) Test pressure used.
(3) Name, address and license number (E#) of the concern.
(4) A written or electronic log shall be maintained of all low-pressure (non-D.O.T.) cylinders which are hydrostatically tested. The log information shall be patterned after the D.O.T. recording requirements and shall include, but will not be limited to: the date, location of extinguisher, type, rating, brand, serial number and the name and EE# of individuals performing the service and the E# of the company they work for.
(d) Hose assemblies. Hose assemblies passing a hydrostatic test do not require recording.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.






s 595. Classifications and Definitions.







s 595.1. Document Transfers.
(a) A license or a Certificate of Registration is not transferable except by the State Fire Marshal.
(b) The State Fire Marshal may transfer a license upon submission of a new license application form and payment of appropriate fees.


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160, 13175, 13178 and 13184, Health and Safety Code.






s 595.2. Expired Documents.
Application for renewal of any class of license or for a Certificate of Registration which has expired shall be considered as an original application.


Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160, 13166, 13167, 13179, 13180, and 13189, Health and Safety Code.






s 595.3. Minimum Ages.
(a) A license shall not be issued to any person under 18 years of age.
(b) A Certificate of Registration shall not be issued to any person under 18 years of age.


Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.








s 595.4. Duplicate Issuance.
A duplicate license or Certificate of Registration may be issued by the State Fire Marshal. A written statement describing the reasons for the duplicate issuance shall be submitted by the licensee or registrant before duplicates will be issued. The statement shall explain fully the reason for the destruction of the license. A fee equal to fifty percent (50%) of the original fee shall be submitted for the issuance of a duplicate certificate of registration.

Note: Authority: Section 13160, Health and Safety Code. Reference: Sections 13160, 13175 and 13183, Health and Safety Code.






s 595.5. Fire Extinguisher License Types.
(a) Types of licenses are as follows:
(1) Type A. A class of license to service any or all types of fire extinguishers including (2), (3), (4), (5), and (6), below.
(2) Type B. A class of license to perform maintenance and recharging of water based fire extinguishers, and external maintenance of carbon dioxide fire extinguishers.

(3) Type C. A class of license to conduct hydrostatic tests of low pressure fire extinguisher cylinders and the fire extinguisher concern shall posses the test equipment as specified in section 594.3(a) for non-D.O.T. specification cylinders. A fire extinguisher concern possessing this class of license shall be a D.O.T. approved cylinder requalification facility if D.O.T. specification cylinders are tested and the fire extinguisher concern shall posses the test equipment as specified in section 594.2.
(4) Type D. A class of license to perform maintenance and recharging of dry chemical, dry powder and external maintenance of halogenated agent fire extinguishers.
(5) Type E. A class of license to conduct hydrostatic tests of high pressure fire extinguisher cylinders, and perform internal maintenance and recharging of carbon dioxide fire extinguishers. A fire extinguisher concern possessing this class of license shall be a DOT approved cylinder requalification facility.
(6) Type F. A class of license to perform internal maintenance, recharge and recover halogenated agents from portable fire extinguishers. A fire extinguisher concern possessing this license shall have a listed Halon 1211 closed recovery system.

(7) Type L. (Limited). A class of license, limited to public or private entities that are not engaged in the business of servicing fire extinguishers and which only maintain their own portable fire extinguishers. A Type L licensee may only perform maintenance of stored pressure dry powder and dry chemical fire extinguishers, water type and wet chemical type fire extinguishers and external annual maintenance of halogenated agent and carbon dioxide fire extinguishers.
(b) Every class of license shall be identified by type as specified above according to the act or acts performed by the licensee or by any of the owner's employees. Every licensed concern shall be staffed by qualified personnel and shall be properly equipped to perform the act or acts for the type of license issued.
(c) Any licensed concern may take orders for the performance of any acts for which the concern is not classified provided these orders are consigned to another licensed concern that is classified (based on 595.5(d)) to perform such acts.
(d) Every licensed concern who is not authorized to perform specific acts shall have on file with the State Fire Marshal reciprocal letters of agreement to perform those specific acts from licensed concerns who are authorized. All required reciprocal letters of agreement shall be submitted to the State Fire Marshal with each original, renewal and status change application for a license. Any changes to reciprocal letters of agreement shall be reported to the State Fire Marshal within 15 days of the change.
(e) A licensee is only authorized to perform those specific acts for which a license has been granted by the State Fire Marshal. Qualifications for a licensee shall consist of having the necessary tools, equipment, service manuals, recharging agents and materials, lubricants, replacement parts and qualified experienced personnel for each specific act. Each licensed concern shall submit evidence of qualifications to the State Fire Marshal with each original, renewal and status change application for license.
(f) A prospective licensee must provide written proof of their service experience in order to be licensed. The prospective licensee shall provide written documentation that they have at least 24 months of experience in the servicing, maintenance, recharging, repairing, hydrostatic testing and installation of portable fire extinguishers. This shall be accomplished by having their fire extinguisher service employer submit letter (s) on their letter head attesting to this experience. This correspondence shall indicate their length of employment, an estimate of the number and type of portable fire extinguishers that they have experience with and a statement that the individual has the necessary experience to obtain a license. Additional documentation mayinclude training certificates from the various fire extinguisher manufacturers and college classes related to Fire Science. (continued)