Loading (50 kb)...'
(continued)
(n) What must I do in the event of a kick? In the event of a kick, you must use one of the following alternatives to dispose of the well-influx fluids giving consideration to personnel safety, possible environmental damage, and possible facility well-equipment damage:
(1) Contain the well-fluid influx by shutting in the well and pumping the fluids back into the formation.
(2) Control the kick by using appropriate well-control techniques to prevent formation fracturing in an open hole within the pressure limits of the well equipment (drill pipe, work string, casing, wellhead, BOP system, and related equipment). The disposal of H2S and other gases must be through pressurized or atmospheric mud-separator equipment depending on volume, pressure and concentration of H2S. The equipment must be designed to recover well-control fluids and burn the gases separated from the well-control fluid. The well-control fluid must be treated to neutralize H2S and restore and maintain the proper quality.
(o) Well testing in a zone known to contain H2S. When testing a well in a zone with H2S present, you must do all of the following:
(1) Before starting a well test, conduct safety meetings for all personnel who will be on the facility during the test. At the meetings, emphasize the use of protective-breathing equipment, first-aid procedures, and the Contingency Plan. Only competent personnel who are trained and are knowledgeable of the hazardous effects of H2S must be engaged in these tests.
(2) Perform well testing with the minimum number of personnel in the immediate vicinity of the rig floor and with the appropriate test equipment to safely and adequately perform the test. During the test, you must continuously monitor H2S levels.
(3) Not burn produced gases except through a flare which meets the requirements of paragraph (q)(6) of this section. Before flaring gas containing H2S, you must activate SO2 monitoring equipment in accordance with paragraph (j)(11) of this section. If you detect SO2 in excess of 2 ppm, you must implement the personnel protective measures in your H2S Contingency Plan, required by paragraph (f)(13)(iv) of this section. You must also follow the requirements of §250.1105. You must pipe gases from stored test fluids into the flare outlet and burn them.
(4) Use downhole test tools and wellhead equipment suitable for H2S service.
(5) Use tubulars suitable for H2S service. You must not use drill pipe for well testing without the prior approval of the District Supervisor. Water cushions must be thoroughly inhibited in order to prevent H2S attack on metals. You must flush the test string fluid treated for this purpose after completion of the test.
(6) Use surface test units and related equipment that is designed for H2S service.
(p) Metallurgical properties of equipment. When operating in a zone with H2S present, you must use equipment that is constructed of materials with metallurgical properties that resist or prevent sulfide stress cracking (also known as hydrogen embrittlement, stress corrosion cracking, or H2S embrittlement), chloride-stress cracking, hydrogen-induced cracking, and other failure modes. You must do all of the following:
(1) Use tubulars and other equipment, casing, tubing, drill pipe, couplings, flanges, and related equipment that is designed for H2S service.
(2) Use BOP system components, wellhead, pressure-control equipment, and related equipment exposed to H2S-bearing fluids in conformance with NACE Standard MR0175–99 (incorporated by reference as specified in §250.198).
(3) Use temporary downhole well-security devices such as retrievable packers and bridge plugs that are designed for H2S service.
(4) When producing in zones bearing H2S, use equipment constructed of materials capable of resisting or preventing sulfide stress cracking.
(5) Keep the use of welding to a minimum during the installation or modification of a production facility. Welding must be done in a manner that ensures resistance to sulfide stress cracking.
(q) General requirements when operating in an H2S zone—(1) Coring operations. When you conduct coring operations in H2S-bearing zones, all personnel in the working area must wear protective-breathing equipment at least 10 stands in advance of retrieving the core barrel. Cores to be transported must be sealed and marked for the presence of H2S.
(2) Logging operations. You must treat and condition well-control fluid in use for logging operations to minimize the effects of H2S on the logging equipment.
(3) Stripping operations. Personnel must monitor displaced well-control fluid returns and wear protective-breathing equipment in the working area when the atmospheric concentration of H2S reaches 20 ppm or if the well is under pressure.
(4) Gas-cut well-control fluid or well kick from H2S-bearing zone. If you decide to circulate out a kick, personnel in the working area during bottoms-up and extended-kill operations must wear protective-breathing equipment.
(5) Drill- and workover-string design and precautions. Drill- and workover-strings must be designed consistent with the anticipated depth, conditions of the hole, and reservoir environment to be encountered. You must minimize exposure of the drill- or workover-string to high stresses as much as practical and consistent with well conditions. Proper handling techniques must be taken to minimize notching and stress concentrations. Precautions must be taken to minimize stresses caused by doglegs, improper stiffness ratios, improper torque, whip, abrasive wear on tool joints, and joint imbalance.
(6) Flare system. The flare outlet must be of a diameter that allows easy nonrestricted flow of gas. You must locate flare line outlets on the downside of the facility and as far from the facility as is feasible, taking into account the prevailing wind directions, the wake effects caused by the facility and adjacent structure(s), and the height of all such facilities and structures. You must equip the flare outlet with an automatic ignition system including a pilot-light gas source or an equivalent system. You must have alternate methods for igniting the flare. You must pipe to the flare system used for H2S all vents from production process equipment, tanks, relief valves, burst plates, and similar devices.
(7) Corrosion mitigation. You must use effective means of monitoring and controlling corrosion caused by acid gases (H2S and CO2) in both the downhole and surface portions of a production system. You must take specific corrosion monitoring and mitigating measures in areas of unusually severe corrosion where accumulation of water and/or higher concentration of H2S exists.
(8) Wireline lubricators. Lubricators which may be exposed to fluids containing H2S must be of H2S-resistant materials.
(9) Fuel and/or instrument gas. You must not use gas containing H2S for instrument gas. You must not use gas containing H2S for fuel gas without the prior approval of the District Supervisor.
(10) Sensing lines and devices. Metals used for sensing line and safety-control devices which are necessarily exposed to H2S-bearing fluids must be constructed of H2S-corrosion resistant materials or coated so as to resist H2S corrosion.
(11) Elastomer seals. You must use H2S-resistant materials for all seals which may be exposed to fluids containing H2S.
(12) Water disposal. If you dispose of produced water by means other than subsurface injection, you must submit to the District Supervisor an analysis of the anticipated H2S content of the water at the final treatment vessel and at the discharge point. The District Supervisor may require that the water be treated for removal of H2S. The District Supervisor may require the submittal of an updated analysis if the water disposal rate or the potential H2S content increases.
(13) Deck drains. You must equip open deck drains with traps or similar devices to prevent the escape of H2S gas into the atmosphere.
(14) Sealed voids. You must take precautions to eliminate sealed spaces in piping designs (e.g., slip-on flanges, reinforcing pads) which can be invaded by atomic hydrogen when H2S is present.
[62 FR 3795, Jan. 27, 1997. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998; 65 FR 15864, Mar. 24, 2000. Redesignated and amended at 68 FR 8423, 8434, Feb. 20, 2003]
Subpart E—Oil and Gas Well-Completion Operations
top
§ 250.500 General requirements.
top
Well-completion operations shall be conducted in a manner to protect against harm or damage to life (including fish and other aquatic life), property, natural resources of the OCS including any mineral deposits (in areas leased and not leased), the national security or defense, or the marine, coastal, or human environment.
§ 250.501 Definition.
top
When used in this subpart, the following term shall have the meaning given below:
Well-completion operations means the work conducted to establish the production of a well after the production-casing string has been set, cemented, and pressure-tested.
§ 250.502 Equipment movement.
top
The movement of well-completion rigs and related equipment on and off a platform or from well to well on the same platform, including rigging up and rigging down, shall be conducted in a safe manner. All wells in the same well-bay which are capable of producing hydrocarbons shall be shut in below the surface with a pump-through-type tubing plug and at the surface with a closed master valve prior to moving well-completion rigs and related equipment, unless otherwise approved by the District Supervisor. A closed surface-controlled subsurface safety valve of the pump-through type may be used in lieu of the pump-through-type tubing plug, provided that the surface control has been locked out of operation. The well from which the rig or related equipment is to be moved shall also be equipped with a back-pressure valve prior to removing the blowout preventer (BOP) system and installing the tree.
[53 FR 10690, Apr. 1, 1988, as amended at 55 FR 47752, Nov. 15, 1990. Redesignated at 63 FR 29479, May 29, 1998]
§ 250.503 Emergency shutdown system.
top
When well-completion operations are conducted on a platform where there are other hydrocarbon-producing wells or other hydrocarbon flow, an emergency shutdown system (ESD) manually controlled station shall be installed near the driller's console or well-servicing unit operator's work station.
§ 250.504 Hydrogen sulfide.
top
When a well-completion operation is conducted in zones known to contain hydrogen sulfide (H2S) or in zones where the presence of H2S is unknown (as defined in §250.490 of this part), the lessee shall take appropriate precautions to protect life and property on the platform or completion unit, including, but not limited to operations such as blowing the well down, dismantling wellhead equipment and flow lines, circulating the well, swabbing, and pulling tubing, pumps, and packers. The lessee shall comply with the requirements in §250.490 of this part as well as the appropriate requirements of this subpart.
[53 FR 10690, Apr. 1, 1988. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998; 68 FR 8434, Feb. 20, 2003]
§ 250.505 Subsea completions.
top
No subsea well completion shall be commenced until the lessee obtains written approval from the District Supervisor in accordance with §250.513 of this part. That approval shall be based upon a case-by-case determination that the proposed equipment and procedures will adequately control the well and permit safe production operations.
[53 FR 10690, Apr. 1, 1988. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998]
§ 250.506 Crew instructions.
top
Prior to engaging in well-completion operations, crew members shall be instructed in the safety requirements of the operations to be performed, possible hazards to be encountered, and general safety considerations to protect personnel, equipment, and the environment. Date and time of safety meetings shall be recorded and available at the facility for review by MMS representatives.
§§ 250.507-250.508 [Reserved]
top
§ 250.509 Well-completion structures on fixed platforms.
top
Derricks, masts, substructures, and related equipment shall be selected, designed, installed, used, and maintained so as to be adequate for the potential loads and conditions of loading that may be encountered during the proposed operations. Prior to moving a well-completion rig or equipment onto a platform, the lessee shall determine the structural capability of the platform to safely support the equipment and proposed operations, taking into consideration the corrosion protection, age of platform, and previous stresses to the platform.
[53 FR 10690, Apr. 1, 1988, as amended at 54 FR 50616, Dec. 8, 1989. Redesignated at 63 FR 29479, May 29, 1998]
§ 250.510 Diesel engine air intakes.
top
No later than May 31, 1989, diesel engine air intakes shall be equipped with a device to shut down the diesel engine in the event of runaway. Diesel engines which are continuously attended shall be equipped with either remote operated manual or automatic-shutdown devices. Diesel engines which are not continuously attended shall be equipped with automatic-shutdown devices.
§ 250.511 Traveling-block safety device.
top
After May 31, 1989, all units being used for well-completion operations which have both a traveling block and a crown block shall be equipped with a safety device which is designed to prevent the traveling block from striking the crown block. The device shall be checked for proper operation weekly and after each drill-line slipping operation. The results of the operational check shall be entered in the operations log.
§ 250.512 Field well-completion rules.
top
When geological and engineering information available in a field enables the District Supervisor to determine specific operating requirements, field well-completion rules may be established on the District Supervisor's initiative or in response to a request from a lessee. Such rules may modify the specific requirements of this subpart. After field well-completion rules have been established, well-completion operations in the field shall be conducted in accordance with such rules and other requirements of this subpart. Field well-completion rules may be amended or canceled for cause at any time upon the initiative of the District Supervisor or upon the request of a lessee.
§ 250.513 Approval and reporting of well-completion operations.
top
Link to an amendment published at 71 FR 19646, April 17, 2006.
(a) No well-completion operation shall begin until the lessee receives written approval from the District Supervisor. If completion is planned and the data are available at the time the Application for Permit to Drill, Form MMS–123 (see §250.410 through §250.418 of this part), is submitted, approval for a well completion may be requested on that form. If the completion has not been approved or if the completion objective or plans have significantly changed, approval for such operations shall be requested on Form MMS–124, Sundry Notices and Reports on Wells.
(b) The following information shall be submitted with Form MMS–124 (or with Form MMS–123):
(1) A brief description of the well-completion procedures to be followed, a statement of the expected surface pressure, and type and weight of completion fluids;
(2) A schematic drawing of the well showing the proposed producing zone(s) and the subsurface well-completion equipment to be used;
(3) For multiple completions, a partial electric log showing the zones proposed for completion, if logs have not been previously submitted; and
(4) When the well-completion is in a zone known to contain H2S or a zone where the presence of H2S is unknown, information pursuant to §250.490 of this part.
(c) Within 30 days after completion, Form MMS–125, Well Summary Report, including a schematic of the tubing and subsurface equipment, shall be submitted to the District Supervisor.
(d) Public information copies of Form MMS–125 shall be submitted in accordance with §250.190.
[53 FR 10690, Apr. 1, 1988, as amended at 58 FR 49928, Sept. 24, 1993. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998; 64 FR 72794, Dec. 28, 1999; 68 FR 8434, Feb. 20, 2003]
§ 250.514 Well-control fluids, equipment, and operations.
top
(a) Well-control fluids, equipment, and operations shall be designed, utilized, maintained, and/or tested as necessary to control the well in foreseeable conditions and circumstances, including subfreezing conditions. The well shall be continuously monitored during well-completion operations and shall not be left unattended at any time unless the well is shut in and secured.
(b) The following well-control-fluid equipment shall be installed, maintained, and utilized:
(1) A fill-up line above the uppermost BOP;
(2) A well-control, fluid-volume measuring device for determining fluid volumes when filling the hole on trips; and
(3) A recording mud-pit-level indicator to determine mud-pit-volume gains and losses. This indicator shall include both a visual and an audible warning device.
(c) When coming out of the hole with drill pipe, the annulus shall be filled with well-control fluid before the change in such fluid level decreases the hydrostatic pressure 75 pounds per square inch (psi) or every five stands of drill pipe, whichever gives a lower decrease in hydrostatic pressure. The number of stands of drill pipe and drill collars that may be pulled prior to filling the hole and the equivalent well-control fluid volume shall be calculated and posted near the operator's station. A mechanical, volumetric, or electronic device for measuring the amount of well-control fluid required to fill the hole shall be utilized.
§ 250.515 Blowout prevention equipment.
top
(a) The BOP system and system components and related well-control equipment shall be designed, used, maintained, and tested in a manner necessary to assure well control in foreseeable conditions and circumstances, including subfreezing conditions. The working pressure rating of the BOP system and BOP system components shall exceed the expected surface pressure to which they may be subjected. If the expected surface pressure exceeds the rated working pressure of the annular preventer, the lessee shall submit with Form MMS–124 or Form MMS–123, as appropriate, a well-control procedure that indicates how the annular preventer will be utilized, and the pressure limitations that will be applied during each mode of pressure control.
(b) The minimum BOP system for well-completion operations must meet the appropriate standards from the following table:
------------------------------------------------------------------------
The minimum BOP stack must
When include
------------------------------------------------------------------------
(1) The expected pressure is less Three BOPs consisting of an
than 5,000 psi. annular, one set of pipe rams,
and one set of blind or blind-
shear rams.
(2) The expected pressure is 5,000 Four BOPs consisting of an
psi or greater or you use multiple annular, two sets of pipe rams,
tubing strings. and one set of blind or blind-
shear rams.
(3) You handle multiple tubing Four BOPs consisting of an
strings simultaneously. annular, one set of pipe rams,
one set of dual pipe rams, and
one set of blind or blind-shear
rams.
(4) You use a tapered drill string... At least one set of pipe rams
that are capable of sealing
around each size of drill
string. If the expected pressure
is greater than 5,000 psi, then
you must have at least two sets
of pipe rams that are capable of
sealing around the larger size
drill string. You may substitute
one set of variable bore rams
for two sets of pipe rams.
(5) It is after February 21, 2006.... At least one set of blind-shear
rams. The blind-shear rams must
be capable of shearing the drill
pipe or tubing in the hole.
------------------------------------------------------------------------
(c) The BOP systems for well completions shall be equipped with the following:
(1) A hydraulic-actuating system that provides sufficient accumulator capacity to supply 1.5 times the volume necessary to close all BOP equipment units with a minimum pressure of 200 psi above the precharge pressure without assistance from a charging system. No later than December 1, 1988, accumulator regulators supplied by rig air and without a secondary source of pneumatic supply, shall be equipped with manual overrides, or alternately, other devices provided to ensure capability of hydraulic operations if rig air is lost.
(2) A secondary power source, independent from the primary power source, with sufficient capacity to close all BOP system components and hold them closed.
(3) Locking devices for the pipe-ram preventers.
(4) At least one remote BOP-control station and one BOP-control station on the rig floor.
(5) A choke line and a kill line each equipped with two full opening valves and a choke manifold. At least one of the valves on the choke line shall be remotely controlled. At least one of the valves on the kill line shall be remotely controlled, except that a check valve on the kill line in lieu of the remotely controlled valve may be installed provided that two readily accessible manual valves are in place and the check valve is placed between the manual valves and the pump. This equipment shall have a pressure rating at least equivalent to the ram preventers.
(d) An inside BOP or a spring-loaded, back-pressure safety valve and an essentially full-opening, work-string safety valve in the open position shall be maintained on the rig floor at all times during well-completion operations. A wrench to fit the work-string safety valve shall be readily available. Proper connections shall be readily available for inserting valves in the work string.
[53 FR 10690, Apr. 1, 1988, as amended at 54 FR 50616, Dec. 8, 1989; 58 FR 49928, Sept. 24, 1993. Redesignated at 62 29479, May 29, 1998, as amended at 68 FR 8434, Feb. 20, 2003]
§ 250.516 Blowout preventer system tests, inspections, and maintenance.
top
(a) BOP pressure testing timeframes. You must pressure test your BOP system:
(1) When installed; and
(2) Before 14 days have elapsed since your last BOP pressure test. You must begin to test your BOP system before 12 a.m. (midnight) on the 14th day following the conclusion of the previous test. However, the District Supervisor may require testing every 7 days if conditions or BOP performance warrant.
(b) BOP test pressures. When you test the BOP system, you must conduct a low pressure and a high pressure test for each BOP component. Each individual pressure test must hold pressure long enough to demonstrate that the tested component(s) holds the required pressure. The District Supervisor may approve or require other test pressures or practices. Required test pressures are as follows:
(1) All low pressure tests must be between 200 and 300 psi. Any initial pressure above 300 psi must be bled back to a pressure between 200 and 300 psi before starting the test. If the initial pressure exceeds 500 psi, you must bleed back to zero and reinitiate the test. You must conduct the low pressure test before the high pressure test.
(2) For ram-type BOP's, choke manifold, and other BOP equipment, the high pressure test must equal the rated working pressure of the equipment.
(3) For annular-type BOP's, the high pressure test must equal 70 percent of the rated working pressure of the equipment.
(c) Duration of pressure test. Each test must hold the required pressure for 5 minutes.
(1) For surface BOP systems and surface equipment of a subsea BOP system, a 3-minute test duration is acceptable if you record your test pressures on the outermost half of a 4-hour chart, on a 1-hour chart, or on a digital recorder.
(2) If the equipment does not hold the required pressure during a test, you must remedy the problem and retest the affected component(s).
(d) Additional BOP testing requirements. You must:
(1) Use water to test the surface BOP system;
(2) Stump test a subsurface BOP system before installation. You must use water to stump test a subsea BOP system. You may use drilling or completion fluids to conduct subsequent tests of a subsea BOP system;
(3) Alternate tests between control stations and pods. If a control station or pod is not functional, you must suspend further completion operations until that station or pod is operable;
(4) Pressure test the blind or blind-shear ram at least every 30 days;
(5) Function test annulars and rams every 7 days;
(6) Pressure-test variable bore-pipe rams against all sizes of pipe in use, excluding drill collars and bottom-hole tools; and
(7) Test affected BOP components following the disconnection or repair of any well-pressure containment seal in the wellhead or BOP stack assembly;
(e) Postponing BOP tests. You may postpone a BOP test if you have well-control problems. You must conduct the required BOP test as soon as possible (i.e., first trip out of the hole) after the problem has been remedied. You must record the reason for postponing any test in the driller's report.
(f) Weekly crew drills. You must conduct a weekly drill to familiarize all personnel engaged in well-completion operations with appropriate safety measures.
(g) BOP inspections. You must visually inspect your BOP system and marine riser at least once each day if weather and sea conditions permit. You may use television cameras to inspect this equipment. The District Supervisor may approve alternate methods and frequencies to inspect a marine riser.
(h) BOP maintenance. You must maintain your BOP system to ensure that the equipment functions properly.
(i) BOP test records. You must record the time, date, and results of all pressure tests, actuations, crew drills, and inspections of the BOP system, system components, and marine riser in the driller's report. In addition, you must:
(1) Record BOP test pressures on pressure charts;
(2) Have your onsite representative certify (sign and date) BOP test charts and reports as correct;
(3) Document the sequential order of BOP and auxiliary equipment testing and the pressure and duration of each test. You may reference a BOP test plan if it is available at the facility;
(4) Identify the control station or pod used during the test;
(5) Identify any problems or irregularities observed during BOP system and equipment testing and record actions taken to remedy the problems or irregularities;
(6) Retain all records including pressure charts, driller's report, and referenced documents pertaining to BOP tests, actuations, and inspections at the facility for the duration of the completion activity; and
(7) After completion of the well, you must retain all the records listed in paragraph (i)(6) of this section for a period of 2 years at the facility, at the lessee's field office nearest the OCS facility, or at another location conveniently available to the District Supervisor.
(j) Alternate methods. The District Supervisor may require, or approve, more frequent testing, as well as different test pressures and inspection methods, or other practices.
[63 FR 29607, June 1, 1998]
§ 250.517 Tubing and wellhead equipment.
top
(a) No tubing string shall be placed in service or continue to be used unless such tubing string has the necessary strength and pressure integrity and is otherwise suitable for its intended use.
(b) In the event of prolonged operations such as milling, fishing, jarring, or washing over that could damage the casing, the casing shall be pressure-tested, calipered, or otherwise evaluated every 30 days and the results submitted to the District Supervisor.
(c) When the tree is installed, the wellhead shall be equipped so that all annuli can be monitored for sustained pressure. If sustained casing pressure is observed on a well, the lessee shall immediately notify the District Supervisor.
(d) Wellhead, tree, and related equipment shall have a pressure rating greater than the shut-in tubing pressure and shall be designed, installed, used, maintained, and tested so as to achieve and maintain pressure control. New wells completed as flowing or gas-lift wells shall be equipped with a minimum of one master valve and one surface safety valve, installed above the master valve, in the vertical run of the tree.
(e) Subsurface safety equipment shall be installed, maintained, and tested in compliance with §250.801 of this part.
[53 FR 10690, Apr. 1, 1988, as amended at 55 FR 47753 Nov. 15, 1990. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998]
Subpart F—Oil and Gas Well-Workover Operations
top
§ 250.600 General requirements.
top
Well-workover operations shall be conducted in a manner to protect against harm or damage to life (including fish and other aquatic life), property, natural resources of the Outer Continental Shelf (OCS) including any mineral deposits (in areas leased and not leased), the national security or defense, or the marine, coastal, or human environment.
§ 250.601 Definitions.
top
When used in this subpart, the following terms shall have the meanings given below:
Expected surface pressure means the highest pressure predicted to be exerted upon the surface of a well. In calculating expected surface pressure, you must consider reservoir pressure as well as applied surface pressure.
Routine operations mean any of the following operations conducted on a well with the tree installed:
(a) Cutting paraffin;
(b) Removing and setting pump-through-type tubing plugs, gas-lift valves, and subsurface safety valves which can be removed by wireline operations;
(c) Bailing sand;
(d) Pressure surveys;
(e) Swabbing;
(f) Scale or corrosion treatment;
(g) Caliper and gauge surveys;
(h) Corrosion inhibitor treatment;
(i) Removing or replacing subsurface pumps;
(j) Through-tubing logging (diagnostics);
(k) Wireline fishing; and
(l) Setting and retrieving other subsurface flow-control devices.
Workover operations mean the work conducted on wells after the initial completion for the purpose of maintaining or restoring the productivity of a well.
[53 FR 10690, Apr. 1, 1988. Redesignated at 63 FR 29479, May 29, 1998, as amended at 71 FR 11313, Mar. 7, 2006]
§ 250.602 Equipment movement.
top
The movement of well-workover rigs and related equipment on and off a platform or from well to well on the same platform, including rigging up and rigging down, shall be conducted in a safe manner. All wells in the same well-bay which are capable of producing hydrocarbons shall be shut in below the surface with a pump-through-type tubing plug and at the surface with a closed master valve prior to moving well-workover rigs and related equipment unless otherwise approved by the District Supervisor. A closed surface-controlled subsurface safety valve of the pump-through-type may be used in lieu of the pump-through-type tubing plug provided that the surface control has been locked out of operation. The well to which a well-workover rig or related equipment is to be moved shall also be equipped with a back-pressure valve prior to removing the tree and installing and testing the blowout-preventer (BOP) system. The well from which a well-workover rig or related equipment is to be moved shall also be equipped with a back pressure valve prior to removing the BOP system and installing the tree. Coiled tubing units, snubbing units, or wireline units may be moved onto a platform without shutting in wells.
§ 250.603 Emergency shutdown system.
top
When well-workover operations are conducted on a well with the tree removed, an emergency shutdown system (ESD) manually controlled station shall be installed near the driller's console or well-servicing unit operator's work station, except when there is no other hydrocarbon-producing well or other hydrocarbon flow on the platform.
§ 250.604 Hydrogen sulfide.
top
When a well-workover operation is conducted in zones known to contain hydrogen sulfide (H2S) or in zones where the presence of H2S is unknown (as defined in §250.490 of this part), the lessee shall take appropriate precautions to protect life and property on the platform or rig, including but not limited to operations such as blowing the well down, dismantling wellhead equipment and flow lines, circulating the well, swabbing, and pulling tubing, pumps and packers. The lessee shall comply with the requirements in §250.490 of this part as well as the appropriate requirements of this subpart.
[53 FR 10690, Apr. 1, 1988. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998; 64 FR 9065, Feb. 24, 1999; 68 FR 8435, Feb. 20, 2003]
§ 250.605 Subsea workovers.
top
No subsea well-workover operation including routine operations shall be commenced until the lessee obtains written approval from the District Supervisor in accordance with §250.613 of this part. That approval shall be based upon a case-by-case determination that the proposed equipment and procedures will maintain adequate control of the well and permit continued safe production operations.
[53 FR 10690, Apr. 1, 1988. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998]
§ 250.606 Crew instructions.
top
Prior to engaging in well-workover operations, crew members shall be instructed in the safety requirements of the operations to be performed, possible hazards to be encountered, and general safety considerations to protect personnel, equipment, and the environment. Date and time of safety meetings shall be recorded and available at the facility for review by a Minerals Management Service representative.
§§ 250.607-250.608 [Reserved]
top
§ 250.609 Well-workover structures on fixed platforms.
top
Derricks, masts, substructures, and related equipment shall be selected, designed, installed, used, and maintained so as to be adequate for the potential loads and conditions of loading that may be encountered during the operations proposed. Prior to moving a well-workover rig or well-servicing equipment onto a platform, the lessee shall determine the structural capability of the platform to safely support the equipment and proposed operations, taking into consideration the corrosion protection, age of the platform, and previous stresses to the platform.
§ 250.610 Diesel engine air intakes.
top
No later than May 31, 1989, diesel engine air intakes shall be equipped with a device to shut down the diesel engine in the event of runaway. Diesel engines which are continuously attended shall be equipped with either remote operated manual or automatic shutdown devices. Diesel engines which are not continuously attended shall be equipped with automatic shutdown devices.
[53 FR 10690, Apr. 1, 1988, as amended at 54 FR 50616, Dec. 8, 1989. Redesignated at 63 FR 29479, May 29, 1998]
§ 250.611 Traveling-block safety device.
top
After May 31, 1989, all units being used for well-workover operations which have both a traveling block and a crown block shall be equipped with a safety device which is designed to prevent the traveling block from striking the crown block. The device shall be checked for proper operation weekly and after each drill-line slipping operation. The results of the operational check shall be entered in the operations log.
§ 250.612 Field well-workover rules.
top
When geological and engineering information available in a field enables the District Supervisor to determine specific operating requirements, field well-workover rules may be established on the District Supervisor's initiative or in response to a request from a lessee. Such rules may modify the specific requirements of this subpart. After field well-workover rules have been established, well-workover operations in the field shall be conducted in accordance with such rules and other requirements of this subpart. Field well-workover rules may be amended or canceled for cause at any time upon the initiative of the District Supervisor or upon the request of a lessee.
§ 250.613 Approval and reporting for well-workover operations.
top
(a) No well-workover operation except routine ones, as defined in §250.601 of this part, shall begin until the lessee receives written approval from the District Supervisor. Approval for such operations shall be requested on Form MMS–124, Sundry Notices and Reports on Wells.
(b) The following information shall be submitted with Form MMS–124:
(1) A brief description of the well-workover procedures to be followed, a statement of the expected surface pressure, and type and weight of workover fluids;
(2) When changes in existing subsurface equipment are proposed, a schematic drawing of the well showing the zone proposed for workover and the workover equipment to be used; and
(3) Where the well-workover is in a zone known to contain H2S or a zone where the presence of H2S is unknown, information pursuant to §250.490 of this part.
(c) The following additional information shall be submitted with Form MMS–124 if completing to a new zone is proposed:
(1) Reason for abandonment of present producing zone including supportive well test data, and
(2) A statement of anticipated or known pressure data for the new zone.
(d) Within 30 days after completing the well-workover operation, except routine operations, Form MMS–124, Sundry Notices and Reports on Wells, shall be submitted to the District Supervisor, showing the work as performed. In the case of a well-workover operation resulting in the initial recompletion of a well into a new zone, a Form MMS–125, Well Summary Report, shall be submitted to the District Supervisor and shall include a new schematic of the tubing subsurface equipment if any subsurface equipment has been changed.
[53 FR 10690, Apr. 1, 1988, as amended at 58 FR 49928, Sept. 24, 1993. Redesignated and amended at 63 FR 29479, 29485, May 29, 1998; 65 FR 35824, June 6, 2000; 68 FR 8435, Feb. 20, 2003]
§ 250.614 Well-control fluids, equipment, and operations.
top
The following requirements apply during all well-workover operations with the tree removed:
(a) Well-control fluids, equipment, and operations shall be designed, utilized, maintained, and/or tested as necessary to control the well in foreseeable conditions and circumstances, including subfreezing conditions. The well shall be continuously monitored during well-workover operations and shall not be left unattended at anytime unless the well is shut in and secured.
(b) When coming out of the hole with drill pipe or a workover string, the annulus shall be filled with well-control fluid before the change in such fluid level decreases the hydrostatic pressure 75 pounds per square inch (psi) or every five stands of drill pipe or workover string, whichever gives a lower decrease in hydrostatic pressure. The number of stands of drill pipe or workover string and drill collars that may be pulled prior to filling the hole and the equivalent well-control fluid volume shall be calculated and posted near the operator's station. A mechanical, volumetric, or electronic device for measuring the amount of well-control fluid required to fill the hold shall be utilized.
(c) The following well-control-fluid equipment shall be installed, maintained, and utilized:
(1) A fill-up line above the uppermost BOP;
(2) A well-control, fluid-volume measuring device for determining fluid volumes when filling the hole on trips; and
(3) A recording mud-pit-level indicator to determine mud-pit-volume gains and losses. This indicator shall include both a visual and an audible warning device.
§ 250.615 Blowout prevention equipment.
top
(a) The BOP system, system components and related well-control equipment shall be designed, used, maintained, and tested in a manner necessary to assure well control in foreseeable conditions and circumstances, including subfreezing conditions. The working pressure rating of the BOP system and system components shall exceed the expected surface pressure to which they may be subjected. If the expected surface pressure exceeds the rated working pressure of the annular preventer, the lessee shall submit with Form MMS–124, requesting approval of the well-workover operation, a well-control procedure that indicates how the annular preventer will be utilized, and the pressure limitations that will be applied during each mode of pressure control.
(b) The minimum BOP system for well-workover operations with the tree removed must meet the appropriate standards from the following table:
------------------------------------------------------------------------
The minimum BOP stack must
When include
------------------------------------------------------------------------
(1) The expected pressure is less Three BOPs consisting of an
than 5,000 psi. annular, one set of pipe rams,
and one set of blind or blind-
shear rams.
(2) The expected pressure is 5,000 Four BOPs consisting of an
psi or greater or you use multiple annular, two sets of pipe rams,
tubing strings. and one set of blind or blind-
shear rams.
(3) You handle multiple tubing Four BOPs consisting of an
strings simultaneously. annular, one set of pipe rams,
one set of dual pipe rams, and
one set of blind or blind-shear
rams.
(4) You use a tapered drill string... At least one set of pipe rams
that are capable of sealing
around each size of drill
string. If the expected pressure
is greater than 5,000 psi, then
you must have at least two sets
of pipe rams that are capable of
sealing around the larger size
drill string. You may substitute
one set of variable bore rams
for two sets of pipe rams.
(5) It is after February 21, 2006.... At least one set of blind-shear
rams. The blind-shear rams must
be capable of shearing the drill
pipe or tubing in the hole.
------------------------------------------------------------------------
(c) The BOP systems for well-workover operations with the tree removed shall be equipped with the following:
(1) A hydraulic-actuating system that provides sufficient accumulator capacity to supply 1.5 times the volume necessary to close all BOP equipment units with a minimum pressure of 200 psi above the precharge pressure without assistance from a charging system. No later than December 1, 1988, accumulator regulators supplied by rig air and without a secondary source of pneumatic supply, shall be equipped with manual overrides, or alternately, other devices provided to ensure capability of hydraulic operations if rig air is lost;
(2) A secondary power source, independent from the primary power source, with sufficient capacity to close all BOP system components and hold them closed;
(3) Locking devices for the pipe-ram preventers;
(4) At least one remote BOP-control station and one BOP-control station on the rig floor; and
(5) A choke line and a kill line each equipped with two full opening valves and a choke manifold. At least one of the valves on the choke-line shall be remotely controlled. At least one of the valves on the kill line shall be remotely controlled, except that a check valve on the kill line in lieu of the remotely controlled valve may be installed provided two readily accessible manual valves are in place and the check valve is placed between the manual valves and the pump. This equipment shall have a pressure rating at least equivalent to the ram preventers.
(d) The minimum BOP-system components for well-workover operations with the tree in place and performed through the wellhead inside of conventional tubing using small-diameter jointed pipe (usually 3/4 inch to 1 1/4 inch) as a work string, i.e., small-tubing operations, shall include the following:
(1) Two sets of pipe rams, and
(2) One set of blind rams.
(e) For coiled tubing operations with the production tree in place, you must meet the following minimum requirements for the BOP system:
(1) BOP system components must be in the following order from the top down:
------------------------------------------------------------------------
BOP system when BOP system for
BOP system when expected surface expected surface wells with returns
pressures are less than or equal pressures are taken through an
to 3,500 psi greater than 3,500 outlet on the BOP
psi stack
------------------------------------------------------------------------
Stripper or annular-type well Stripper or Stripper or
control component. annular-type well annular-type well
control component. control
component.
Hydraulically-operated blind Hydraulically- Hydraulically-
rams. operated blind operated blind
rams. rams.
Hydraulically-operated shear Hydraulically- Hydraulically-
rams. operated shear operated shear
rams. rams.
Kill line inlet................. Kill line inlet... Kill line inlet.
Hydraulically-operated two-way Hydraulically- Hydraulically-
slip rams. operated two-way operated two-way
slip rams. slip rams.
Hydraulically-operated pipe rams Hydraulically- A flow tee or
operated pipe cross.
rams.. Hydraulically-
Hydraulically- operated pipe
operated blind- rams.
shear rams. These Hydraulically-
rams should be operated blind-
located as close shear rams on
to the tree as wells with
practical. surface pressures
>3,500 psi. As
an option, the
pipe rams can be
placed below the
blind-shear rams.
The blind-shear
rams should be
located as close
to the tree as
practical.
------------------------------------------------------------------------
(2) You may use a set of hydraulically-operated combination rams for the blind rams and shear rams.
(3) You may use a set of hydraulically-operated combination rams for the hydraulic two-way slip rams and the hydraulically-operated pipe rams.
(4) You must attach a dual check valve assembly to the coiled tubing connector at the downhole end of the coiled tubing string for all coiled tubing well-workover operations. If you plan to conduct operations without downhole check valves, you must describe alternate procedures and equipment in Form MMS–124, Application for Permit to Modify and have it approved by the District Manager.
(5) You must have a kill line and a separate choke line. You must equip each line with two full-opening valves and at least one of the valves must be remotely controlled. You may use a manual valve instead of the remotely controlled valve on the kill line if you install a check valve between the two full-opening manual valves and the pump or manifold. The valves must have a working pressurerating equal to or greater than the working pressure rating of the connection to which they are attached, and you must install them between the well control stack and the choke or kill line. For operations with expected surface pressures greater than 3,500 psi, the kill line must be connected to a pump or manifold. You must not use the kill line inlet on the BOP stack for taking fluid returns from the wellbore. (continued)