Loading (50 kb)...'
(continued)
§ 108.423 Fire hydrants and associated equipment.
top
(a) A fire main system must have enough fire hydrants so that each accessible space may be sprayed with at least two spray patterns of water.
(b) In a main machinery space, except a shaft alley with no assigned space for stowage of combustibles, each spray pattern of water must be from one length of fire hose and each must be from a separate outlet. In all other spaces at least one spray pattern of water must be from one length of fire hose.
(c) No outlet on a fire hydrant may point above the horizontal.
(d) Each fire hydrant must have at least one spanner and at least one fire hose rack or reel.
§ 108.425 Fire hoses and associated equipment.
top
(a) Each length of fire hose in a fire main system must be—
(1) Of 1 1/2 or 2 1/2 inch nominal hose size diameter;
(2) Of 50 foot nominal hose size length; and
(3) Lined commercial fire hose that meets Standard 19 of the Underwriters' Laboratories, Inc., (1971 edition) or Federal Specification ZZ-H-451f.
(b) Fire station hydrant connections shall be brass, bronze, or other equivalent metal. Couplings shall either:
(1) Use National Standard fire hose coupling threads for the 1 1/2 inch (38 millimeter) and 2 1/2 inch (64 millimeter) hose sizes, i.e., 9 threads per inch for 1 1/2 inch hose, and 7 1/2 threads per inch for 2 1/2 inch hose; or
(2) Be a uniform design for each hose diameter throughout the vessel.
(c) Each nozzle for a firehose in a fire main system must be a combination solid stream and water spray firehose nozzle that is approve under subpart 162.027. Combination solid stream and water spray nozzles previously approved under subpart 162.027 of this chapter may be retained so long as they are maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection.
(d) A combination solid stream and water spray firehose nozzle previously approved under subpart 162.027 of this chapter, must have a low-velocity water spray applicator also previously approved under subpart 162.027 of this chapter when installed in—
(1) Machinery spaces containing oil fired boilers, internal combustion machinery or oil fuel units; and
(2) Helicopter decks.
[CGD 73–251, 43 FR 56808, Dec. 4, 1978, as amended by CGD 95–027, 61 FR 26008, May 23, 1996; CGD 95–028, 62 FR 51208, Sept. 30, 1997]
§ 108.427 International shore connection.
top
A fire main system on a unit in international service must have—
(a) At least one international shore connection that meets ASTM F 1121 (incorporated by reference, see §105.01–3).
(b) A cutoff valve and check valve for each connection; and
(c) Facilities available enabling the connection to be used on either side of the unit.
[CGD 73–251, 43 FR 56808, Dec. 4, 1978, as amended by CGD 88–032, 56 FR 35826, July 29, 1991; USCG–2000–7790, 65 FR 58462, Sept. 29, 2000]
§ 108.429 Fire main system protection.
top
(a) Each pipe and fire hydrant in a fire main system must be installed to the extent practicable in locations that are not exposed to damage by materials that are moved on or onto the deck.
(b) Each part of the fire main system located on an exposed deck must either be protected against freezing or be fitted with cutout valves and drain valves to shut off and drain the entire exposed system in freezing weather.
Automatic Sprinkling Systems
top
§ 108.430 General.
top
Automatic Sprinkler Systems shall comply with NFPA 13–1996.
[CGD 95–028, 62 FR 51208, Sept. 30, 1997]
Fixed Carbon Dioxide Fire Extinguishing Systems
top
§ 108.431 Carbon dioxide systems: General.
top
(a) Sections 108.431 through 108.457 apply to high pressure carbon dioxide fire extinguishing systems.
(b) Low pressure systems, that is, those in which the carbon dioxide is stored in liquid form at low temperature, must be approved by the Commandant.
(c) Each carbon dioxide system cylinder must be fabricated, tested, and marked in accordance with §§147.60 and 147.65 of this chapter.
[CGD 73–251, 43 FR 56808, Dec. 4, 1978, as amended by CGD 84–044, 53 FR 7749, Mar. 10, 1988]
§ 108.433 Quantity of CO2: General.
top
Each CO2 system must have enough gas to meet the quantity requirements of §108.439 for the space requiring the greatest amount of CO2.
§ 108.437 Pipe sizes and discharge rates for enclosed ventilation systems for rotating electrical equipment.
top
(a) The minimum pipe size for the initial charge must meet table 108.441 and the discharge of the required amount of CO2 must be completed within 2 minutes.
(b) The minimum pipe size for the delayed discharge must be at least 1.25 centimeters ( 1/2 inch) standard pipe.
(c) The pipe used for the initial discharge must not be used for the delayed discharge, except systems having a volume of less than 57 cubic meters (2,000 cubic feet).
§ 108.439 Quantity of CO2 for protection of spaces.
top
(a) The number of pounds of CO2 required to protect a space must be equal to the gross volume of the space divided by the appropriate factor from Table 108.439.
(b) If a machinery space includes a casing, the gross volume of the space may be calculated using the reductions allowed in 46 CFR 95.10–5(e).
(c) If fuel can drain from a space to an adjacent space or if two spaces are not entirely separate, the requirements for both spaces must be used to determine the amount of CO2 to be provided and the CO2 system must be arranged to discharge into both spaces simultaneously.
Table 108.439_CO2 Supply Factors
[Gross volume of space in cubic feet]
------------------------------------------------------------------------
Over Not over Factor
------------------------------------------------------------------------
0................................................. 500 15
500............................................... 1,600 16
1,600............................................. 4,500 18
4,500............................................. 50,000 20
50,000............................................ ......... 22
------------------------------------------------------------------------
§ 108.441 Piping and discharge rates for CO2 systems.
top
(a) The size of branch lines to spaces protected by a CO2 system must meet Table 108.441.
(b) Distribution piping within a space must be proportioned from the supply line to give proper distribution to the outlets without throttling.
(c) The number, type, and location of discharge outlets must distribute the CO2 uniformly throughout the space.
Table 108.441_CO2 System Pipe Size
------------------------------------------------------------------------
Minimum pipe size (inches),
CO2 supply in system, kilograms (pounds) millimeters (inches)
------------------------------------------------------------------------
45 (100).................................. 12.7 (\1/2\).
104 (225)................................. 19.05 (\3/4\).
136 (300)................................. 25.4 (1).
272 (600)................................. 31.75 (1\1/4\).
450 (1,000)............................... 38.10 (1\1/2\).
1,110 (2,450)............................. 50.80 (2).
1,130 (2,500)............................. 63.5 (2\1/2\).
2,023 (4,450)............................. 76.2 (3).
3,229 (7,100)............................. 88.9 (3\1/2\).
4,750 (10,000)............................ 101.6 (4).
6,818 (15,000)............................ 114.3 (4\1/2\).
------------------------------------------------------------------------
(d) The total area of all discharge outlets must be more than 35 percent and less than 85 percent of the nominal cylinder outlet area or the area of the supply pipe, whichever is smaller. The nominal cylinder outlet area in square centimeters is determined by multiplying the factor 0.0313 by the number of kilograms of CO2 required. (The nominal cylinder outlet area in square inches is determined by multiplying the factor 0.0022 by the number of pounds of CO2 required). The nominal cylinder outlet area must not be less than 71 square millimeters (0.110 square inches).
(e) A CO2 system must discharge at least 85 percent of the required amount within 2 minutes.
§ 108.443 Controls and valves.
top
(a) At least one control for operating a CO2 system must be outside the space or spaces that the system protects and in a location that would be accessible if a fire occurred in any space that the system protects. Control valves must not be located in a protected space unless the CO2 cylinders are also in the protected space.
(b) A CO2 system that protects more than one space must have a manifold with a stop valve, the normal position of which is closed, that directs the flow of CO2 to each protected space.
(c) A CO2 system that protects only one space must have a stop valve installed between the cylinders and the discharge outlets in the system, except on a system that has a CO2 supply of 136 kilograms (300 pounds) or less.
(d) At least one of the control stations in a CO2 system that protects a machinery space must be as near as practicable to one of the main escapes from that space.
(e) All distribution valves and controls must be of an approved type.
(f) Each CO2 system that has a stop valve must have a remote control that operates only the stop valve and must have a separate remote control for releasing the required amount of CO2 into the space protected by the system.
(g) Each CO2 system that does not have a stop valve must be operated by a remote control that releases the required amount of CO2 into the space protected by the system.
(h) Remote controls to each space must be in an enclosure.
(i) Each system must have a manual control at its cylinders for releasing CO2 from the cylinders, except that if the system has pilot cylinders, a manual control is not required for other than pilot cylinders.
(j) If gas pressure is used to release CO2 from a system having more than 2 cylinders, the system must have at least 2 pilot cylinders to release the CO2 from the remaining cylinders.
(k) If the entrance to a space containing the CO2 supply or controls of a CO2 system has a lock, the space must have a key to the lock in a break-glass type box that is next to and visible from the entrance.
§ 108.445 Alarm and means of escape.
top
(a) Each CO2 system that has a supply of more than 136 kilograms (300 pounds) of CO2, except a system that protects a tank, must have an alarm that sounds for at least 20 seconds before the CO2 is released into the space.
(b) Each audible alarm for a CO2 system must have the CO2 supply for the system as its source of power and must be in a visible location in the spaces protected.
§ 108.447 Piping.
top
(a) Each pipe, valve, and fitting in a CO2 system must have a bursting pressure of at least 420 kilograms per square centimeter (6,000 pounds per square inch).
(b) All piping for a CO2 system of nominal size of 19.05 millimeters ( 3/4 inch) inside diameter or less must be at least Schedule 40 (standard weight) and all piping of nominal size over 19.05 millimeters ( 3/4 inch) inside diameter must be at least Schedule 80 (extra heavy).
(c) Each pipe, valve, and fitting made of ferrous materials in a CO2 system must be protected inside and outside from corrosion.
(d) Each CO2 system must have a pressure relief valve set to relieve between 168 and 196 kilograms per square centimeter (2,400 and 2,800 pounds per square inch) in the distribution manifold or other location that protects the piping when all branch line shut off valves are closed.
(e) The end of each branch line in a CO2 system must extend at least 50 millimeters (2 inches) beyond the last discharge outlet and be closed with a cap or plug.
(f) Piping, valves, and fittings in a CO2 system must be securely supported and protected from damage.
(g) Each CO2 system must have drains and dirt traps located where dirt or moisture can accumulate in the system.
(h) Discharge piping in a CO2 system may not be used for any other purpose except as part of a fire detection system.
(i) Piping in a CO2 system that passes through accommodation spaces must not have drains or other openings within these spaces.
§ 108.449 Piping tests.
top
(a) Each test prescribed in (b), (c), and (d) of this section must be performed upon completion of the piping installation.
(b) When tested with CO2 or other inert gas under a pressure of 70 kilograms per square centimeter (1000 pounds per square inch), with no additional gas introduced into the system, the leakage in the piping from the cylinders to the stop valves in the manifold must not allow a pressure drop of more than 10.5 kilograms per square centimeter (150 pounds per square inch) per minute for a 2 minute period.
(c) When tested with CO2 or other inert gas under a pressure of 42 kilograms per square centimeter (600 pounds per square inch), with no additional gas introduced into the system, the leakage in each branch line must not allow a pressure drop of more than 10.5 kilograms per square centimeter (150 pounds per square inch) per minute for a 2-minute period. The distribution piping must be capped within the protected space.
(d) Small independent systems protecting emergency generator rooms, lamp lockers and similar small spaces need not meet the tests prescribed in paragraphs (a) and (b) of this section if they are tested by blowing out the piping with air at a pressure of at least 7 kilograms per square centimeter (100 pounds per square inch).
§ 108.451 CO2 storage.
top
(a) Except as provided in paragraph (b) of this section, each cylinder of a CO2 system must be outside each space protected by the system and in a location that would be accessible if a fire occurred in any space protected by the system.
(b) A CO2 system that has a CO2 supply of 136 kilograms (300 pounds) or less may have one or more cylinders in the space protected by the system if the space has a heat detection system to activate the system automatically in addition to the remote and manual controls required by this subpart.
(c) Each space that contains cylinders of a CO2 system must be ventilated and designed to prevent an ambient temperature of more than 54° C. (130° F.)
(d) Each cylinder in a CO2 system must be securely fastened, supported, protected from damage, in an accessible location, and capable of removal from that location.
(e) Each unit must have a means for weighing cylinders of a CO2 system.
(f) A cylinder in a CO2 system may not be mounted in a position that is inclined more than 30° from a vertical position, except that a cylinder having flexible or bent siphon tubes may be mounted in a position that is inclined up to 80° from the vertical. The bottom of each cylinder when mounted must be at least 5 centimeters (2 inches) from the deck.
(g) If a cylinder does not have a check valve on its independent cylinder discharge, it must have a plug or cap to close the outlet when the cylinder is moved.
[CGD 73–251, 43 FR 56808, Dec. 4, 1978, as amended by CGD 84–044, 53 FR 7749, Mar. 10, 1988]
§ 108.453 Discharge outlets.
top
Each discharge outlet must be of an approved type.
§ 108.455 Enclosure openings.
top
(a) Mechanical ventilation for spaces protected by a CO2 system must be designed to shut down automatically when the system is activated.
(b) Each space that is protected by a CO2 system and that has natural ventilation must have a means for closing that ventilation.
(c) Each space protected by a CO2 system must have the following means for closing the openings to the space from outside the space:
(1) Doors, shutters, or dampers for closing each opening in the lower portion of the space.
(2) Doors, shutters, dampers or temporary means such as canvas or other material normally on board a unit may be used for closing each opening in the upper portion of the space.
§ 108.457 Pressure release.
top
Each air tight or vapor tight space, such as a paint locker, that is protected by a CO2 system must have a means for releasing pressure that accumulates within the space if CO2 is discharged into the space.
Halogenated Gas Extinguishing Systems
top
§ 108.458 General.
top
Halogenated gas extinguishing systems may be installed if approved by the Commandant.
Foam Extinguishing Systems
top
§ 108.459 Number and location of outlets.
top
(a) A foam extinguishing system in a space must have enough outlets to spread a layer of foam of uniform thickness over the deck or bilge areas of the space.
(b) A foam extinguishing system in a space that has a boiler on a flat that is open to or can drain into a lower portion of the space must have enough outlets to spread a layer of foam of uniform thickness over the—
(1) Flat; and
(2) Deck or bilge areas of the space.
(c) A foam extinguishing system for a tank must have enough outlets to spread a layer of foam of uniform thickness over the surface of the liquid in the tank.
§ 108.461 Coamings.
top
Each machinery flat in a space that has a foam extinguishing system must have coamings that are high enough to retain spilled oil and foam on the flat on all openings except deck drains.
§ 108.463 Foam rate: Protein.
top
(a) If the outlets of a protein foam extinguishing system are in a space, the foam rate at each outlet must be at least 6.52 liters per minute for each square meter (.16 gallons per minute for each square foot) of area covered by the systems.
(b) If the outlets of a protein foam extinguishing system are in a tank, the foam rate at each outlet must be at least 4.07 liters per minute for each square meter (.1 gallon per minute for each square foot) of liquid surface in the tank.
§ 108.467 Water supply.
top
The water supply of a foam extinguishing system must not be the water supply of the fire main system on the unit unless when both systems are operated simultaneously—
(a) The water supply rate to the foam production equipment meets the requirements of this section; and
(b) Water supply rate to the fire hydrants required by §108.415 of this subpart allows compliance with the pressure requirement in that section.
§ 108.469 Quantity of foam producing materials.
top
(a) Except as provided in paragraph (b) of this section, each foam extinguishing system with outlets—
(1) In a tank must have enough foam producing material to discharge foam for at least 5 minutes at each outlet; and
(2) In a space must have enough foam producing material to discharge foam for at least 3 minutes at each outlet.
(b) If a foam system has outlets in more than one tank or space, the system need have only enough foam producing material to cover the largest space that the system covers or, if the liquid surface of a tank covered by the system is larger, the tank with the largest liquid surface.
§ 108.471 Water pump.
top
Each water pump in a foam extinguishing system must be outside each machinery space in which the system has outlets and must not receive power from any of those spaces.
§ 108.473 Foam system components.
top
(a) Each foam agent, each tank for a foam agent, each discharge outlet, each control, and each valve for the operation of a foam extinguishing system must be approved by the Commandant.
(b) Each foam agent tank and each control and valve for the operation of a foam extinguishing system with outlets in a space must be outside the space and must not be in a space that may become inaccessible if a fire occurs in the space.
(c) Each control for a foam extinguishing system with outlets in a space must be near a main escape from the space.
§ 108.474 Aqueous film forming foam systems.
top
Aqueous film forming foam systems may be installed if approved by the Commandant.
§ 108.475 Piping.
top
(a) Each pipe, valve, and fitting in a foam extinguishing system must meet the applicable requirements in Subchapter F of this chapter.
(b) Each pipe, valve, and fitting made of ferrous material must be protected inside and outside from corrosion.
(c) Each pipe, valve, and fitting must have support and protection from damage.
(d) Each foam extinguishing system must have enough—
(1) Dirt traps to prevent the accumulation of dirt in its pipes; and
(2) Drains to remove liquid from the system.
(e) Piping in a foam extinguishing system must be used only for discharging foam.
§ 108.477 Fire hydrants.
top
(a) If a fixed foam extinguishing system has outlets in a main machinery space, at least 2 fire hydrants, in addition to the fire hydrants required by §108.423 of this subpart, must be installed outside the entrances to the space with each at a separate entrance.
(b) Each hydrant must have enough hose to spray any part of the space.
(c) Each hydrant must have a combination nozzle and applicator.
Fire Protection for Helicopter Facilities
top
§ 108.486 Helicopter decks.
top
At least two of the accesses to the helicopter landing deck must each have a fire hydrant on the unit's fire main system located next to them.
§ 108.487 Helicopter deck fueling operations.
top
(a) Each helicopter landing deck on which fueling operations are conducted must have a fire protection system that discharges protein foam or aqueous film forming foam.
(b) a system that only discharges foam must—
(1) Have enough foam agent to discharge foam continuously for at least 5 minutes at maximum discharge rate;
(2) Have at least the amount of foam agent needed to cover an area equivalent to the swept rotor area of the largest helicopter for which the deck is designed with foam at—
(i) If protein foam is used, 6.52 liters per minute for each square meter (.16 gallons per minute for each square foot) of area covered for five minutes;
(ii) If aqueous film forming foam is used, 4.07 liters per minute for each square meter (.1 gallons per minute for each square foot) of area covered for five minutes; and
(3) Be capable of discharging from each hose at 7 kilograms per square centimeter (100 pounds per square inch) pressure—
(i) A single foam stream at a rate of at least 340 liters (90 gallons) per minute; and
(ii) A foam spray at a rate of at least 190 liters (50 gallons) per minute.
(c) Each system must have operating controls at each of its hose locations, be protected from icing and freezing, and be capable of operation within 10 seconds after activation of its controls.
(d) Each system must have at least one hose at each of the two access routes required by §108.235(f) of this part. Each hose must be reel mounted and long enough to cover any point on the helicopter deck. Each hose that discharges foam must have a nozzle that has foam stream, foam spray, and off positions.
§ 108.489 Helicopter fueling facilities.
top
(a) Each helicopter fueling facility must have a fire protection system that discharges one of the following agents in the amounts prescribed for the agents over the area of the fuel containment systems around marine portable tanks, fuel transfer pumps and fuel hose reels:
(1) Protein foam at the rate of 6.52 liters per minute for each square meter (.16 gallons per minute for each square foot) of area covered for five minutes.
(2) Aqueous film forming foam at the rate of 4.07 liters per minute for each square meter (.1 gallon per minute for each square foot) of area covered for five minutes.
(3) 22.5 kilograms (50 pounds) of dry chemical (B-V semi-portable) for each fueling facility of up to 27.87 square meters (300 square feet).
(b) If the fire protection system required by §108.487 of this subpart is arranged so that it covers both a helicopter fueling facility and a landing deck, the system must have the quantity of agents required by this section in addition to the quantity required by §108.487.
Hand Portable and Semiportable Fire Extinguishing Systems
top
§ 108.491 General.
top
Each hand portable and semiportable fire extinguisher on a unit must be approved under Subpart 162.028 or 162.039 of this chapter.
§ 108.493 Location.
top
(a) Each unit must have the hand portable and semiportable fire extinguishers prescribed in Table 108.495(a) of this subpart and installed in the locations prescribed in the table.
(b) Each portable and semi-portable fire extinguisher must be visible and readily accessible.
(c) The location, size, and number of each portable and semiportable fire extinguisher on a unit must be acceptable to the appropriate OCMI. The OCMI may require extinguishers in addition to those prescribed in Table 108.495(a) if he considers them necessary for fire protection on the unit.
(d) Each hand portable and semiportable fire extinguisher that has a nameplate which states that it is to be protected from freezing, must be located where freezing temperatures do not occur.
§ 108.495 Spare charges.
top
(a) Each unit must have enough spare charges for 50 percent of the hand portable fire extinguishers required under Table 108.495(a) of this subpart that are rechargeable by personnel on the unit.
(b) If a unit has extinguishers that cannot be recharged by personnel on unit, it must also have at least one spare extinguisher for each classification and variety of those extinguishers.
Table 108.495(a)_Hand Portable Fire Extinguishers and Semiportable Fire-
Extinguishing Systems
------------------------------------------------------------------------
Classification
Space (see table Quantity and location
108.495(b))
------------------------------------------------------------------------
safety areas
Wheelhouse and control room... C-I............. 2 in vicinity of
exit.
Stairway and elevator ................. None required.
enclosure.
Corridors..................... A-II............ 1 in each corridor
not more than 150 ft
(45 m) apart. (May
be located in
stairways.)
Lifeboat embarkation and ................. None required.
lowering stations.
Radio room.................... C-I............. 2 in vicinity of
exit.
accommodations
Staterooms, toilet spaces, ................. None required.
public spaces, offices,
lockers, small storerooms,
and pantries, open decks, and
similar spaces.
service spaces
Galleys....................... B-II or C-II.... 1 for each 2,500 ft
\2\ (232 m \2\ ) or
fraction thereof
suitable for hazards
involved.
Paint and lamp rooms.......... B-II............ 1 outside each room
in vicinity of exit.
Storerooms.................... A-II............ 1 for each 2,500 ft
\2\ (232 m \2\ ) or
fraction thereof
located in vicinity
of exits, either
inside or outside
the spaces.
Work shop and similar spaces.. C-II............ 1 outside each space
in vicinity of an
exit.
machinery spaces
Oil-fired boilers: Spaces B-II............ 2 required in each
containing oil-fired boilers, B-V.............. space.
either main or auxiliary, or 1 required in each
their fuel oil units. space.
Internal combustion or gas B-II............ 1 for each 1,000
turbine propelling machinery brake horsepower but
spaces. not less than 2 nor
more than 6 in each
space.
B-III........... 1 required in each
space. See note 1.
Motors or generators of C-II............ 1 for each motor or
electric propelling machinery generator.
that do not have an enclosed
ventilating system.
Motors and generators of ................. None required.
electric propelling machinery
that have enclosed
ventilating systems.
auxiliary spaces
Internal combustion engines or B-II............ Outside the space
gas turbine. containing engines
or turbines in
vicinity of exit.
Electric emergency motors or C-II............ 1 outside the space
generators. containing motors or
generators in
vicinity of exit.
Steam driven auxiliary ................. None required.
machinery.
Trunks to machinery spaces.... ................. Do.
Fuel tanks.................... ................. Do.
miscellaneous areas
Helicopter landing decks...... B-V............. 1 at each access
route.
Helicopter fueling facilities. B-IV............ 1 at each fuel
transfer facility.
See note 2.
Drill floor................... C-II............ 2 required.
Cranes with internal B-II............ 1 required.
combustion engines.
------------------------------------------------------------------------
Notes: 1. Not required where a fixed gas extinguishing system is
installed.
2. Not required where a fixed foam system is installed in accordance
with § 108.489 of this subpart.
Table 108.495(b)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Classification: Water liters Foam liters Carbon dioxide Dry chemical Halon 1211
Type and size (gallons) (gallons) kilograms (pounds) kilograms (pounds) kilograms (pounds)
--------------------------------------------------------------------------------------------------------------------------------------------------------
A............................... II................ 9.5 (2\1/2\)...... 9.5 (2\1/2\)...... .................. 2.25 (5) \3\......
B............................... I................. .................. 4.7 (1\1/4\)...... 1.8 (4)........... 0.9 (2)........... 1.1 (2\1/2\)
B............................... II................ .................. 9.5 (2\1/2\)...... 6.7 (15).......... 4.5 (10).......... 4.5 (10) \5\
B............................... III............... .................. 45.5 (12)......... 15.8 (35)......... 9.0 (20)..........
B............................... IV................ .................. 7.6 (20).......... 22.5 (50)......... 13.5 (30).........
B............................... V................. .................. 152 (40).......... 45 (100) \4\...... 22.5 (50) \4\.....
C............................... I................. .................. .................. 1.8 (4)........... 0.9 (2)...........
C............................... II................ .................. .................. 6.7 (15).......... 4.5 (10)..........
C............................... III............... .................. .................. 15.8 (35)......... 9.0 (20)..........
C............................... IV................ .................. .................. 22.5 (50)......... 13.5 (30).........
--------------------------------------------------------------------------------------------------------------------------------------------------------
Note: 1. Fire extinguishers are designed by type as follows: (a) ``A'' for fires in combustible materials such as wood. (b) ``B'' for fires in flammable
liquids and greases. (c) ``C'' for fires in electrical equipment.
2. Fire extinguishers are designated by size where size ``I'' is the smallest and size ``V'' is the largest. Sizes ``I'' and ``II'' are hand-portable
extinguishers and sizes ``III'', ``IV'', and ``V'' are semiportable extinguishers.
3. Must be specifically approved as a type A, B, or C extinguisher.
4. For outside use, double the quantity of agent that must be carried.
5. For outside use only.
§ 108.496 Semiportable fire extinguishers.
top
(a) The frame or support of each size III, IV, and V fire extinguisher required by Table 108.495(a), except a wheeled size V extinguisher provided for a helicopter landing deck, must be welded or otherwise permanently attached to a bulkhead or deck.
(b) If the following semiportable fire extinguishers have wheels, they must be securely stowed when not in use to prevent them from rolling out of control under heavy sea conditions:
(1) Each size V extinguisher required for a helicopter landing deck.
(2) Each size III, IV, and V extinguisher that is not required by Table 108.495(a).
[CGD 77–039, 44 FR 34133, June 14, 1979]
Miscellaneous Firefighting Equipment
top
§ 108.497 Fireman's outfits.
top
Each unit must have at least 2 fireman's outfits. Each fireman's outfit on a unit must consist of—
(a) A pressure-demand, open-circuit, self-contained breathing apparatus, approved by the Mine Safety and Health Administration (MSHA) and by the National Institute for Occupational Safety and Health (NIOSH) and having at a minimum a 30-minute air supply, a full facepiece, and a spare charge; but a self-contained compressed-air breathing apparatus previously approved by MSHA and NIOSH under part 160, subpart 160.011, of this chapter may continue in use as required equipment if it was part of the vessel's equipment on November 23, 1992, and as long as it is maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection;
(b) A Type II or Type III flashlight constructed and marked in accordance with ASTM F 1014 (incorporated by reference, see §108.101).
(c) An oxygen and explosive meter with the Underwriter's Laboratories, Inc. label or the Factory Mutual label;
(d) A lifeline that—
(1) Is attached to a belt or a suitable harness;
(2) Is made of bronze wire rope, inherently corrosion resistant steel wire rope, or galvanized or tinned steel wire rope;
(3) Is made up of enough 15.2 meters (50 foot) or greater lengths of wire rope to permit use of the outfit in any location on the unit;
(4) Has each end fitted with a hook with a 16 millimeters ( 5/8 inch) throat opening for the keeper; and
(5) Has a minimum breaking strength of 680 kilograms (1,500 pounds).
(e) Boots and gloves that are made of rubber or other electrically non-conductive material;
(f) A helmet that meets the requirements in ANSI standard Z–89.1–1969; and
(g) Clothing that protects the skin from scalding steam and the heat of fire and that has a water resistant outer surface.
[CGD 73–251, 43 FR 56808, Dec. 4, 1978, as amended by CGD 82–042, 53 FR 17705, May 18, 1988; CGD 86–036, 57 FR 48326, Oct. 23, 1992; USCG 1999–5151, 64 FR 67182, Dec. 1, 1999]
§ 108.499 Fire axes.
top
Each unit must have at least two fire axes.
Subpart E—Lifesaving Equipment
top
Source: CGD 84–069, 61 FR 25291, May 20, 1996, unless otherwise noted.
§ 108.500 General.
top
(a) Each unit, other than a drillship, must meet the requirements in this subpart.
(b) Each drillship must meet the lifesaving system requirements in subchapter W of this chapter for a tank vessel certificated to carry cargoes that have a flash point less than 60° C as determined under ASTM D 93 (incorporated by reference, see §108.101).
(c) The OCMI may require a unit to carry specialized or additional lifesaving equipment other than as required by this part, if the OCMI determines the conditions of the unit's service present uniquely hazardous circumstances which are not adequately addressed by existing requirements.
[CGD 84–069, 61 FR 25291, May 20, 1996, as amended at 63 FR 52814, Oct. 1, 1998; USCG 1999–5151, 64 FR 67182, Dec. 1, 1999]
§ 108.503 Relationship to international standards.
top
For the purposes of this part, any unit carrying a valid IMO MODU Safety Certificate, including a listing of lifesaving equipment as required by the 1989 IMO MODU Code, is considered to have met the requirements of this subpart if, in addition to the requirements of the 1989 IMO MODU Code, it meets the following requirements:
(a) Each new lifeboat and launching appliance may be of aluminum construction only if its stowage location is protected with a water spray system in accordance with §108.550(d) of this chapter.
(b) Each lifejacket, immersion suit, and emergency position indicating radiobeacon (EPIRB) must be marked with the unit's name in accordance with §§108.649 and 108.650.
(c) Inflatable lifejackets, if carried, must be of the same or similar design as required by §108.580(b).
(d) Containers for lifejackets, immersions suits, and anti-exposure suits must be marked as specified in §108.649(g).
(e) Each liferaft must be arranged to permit it to drop into the water from the deck on which it is stowed as required in §108.530(c)(3).
(f) Survival craft must be arranged to allow safe disembarkation onto the unit after a drill in accordance with §108.540(f).
(g) The requirements for guarding of falls in §§108.553 (d) and (f) must be met.
(h) The winch drum requirements described in §108.553(e) must be met for all survival craft winches, not just multiple drum winches.
(i) The maximum lowering speed requirements from §§108.553 (h) and (i) must be met.
(j) An auxiliary line must be kept with each line-throwing appliance in accordance with §108.597(c)(2).
(k) Immersion suits are required on all units, except those operating between the 32 degrees north and 32 degrees south latitude in accordance with §108.580(c).
(l) All abandonment drills conducted on units carrying immersion suits must include immersion suits.
§ 108.510 Application.
top
(a) For the purposes of this subpart—
(1) Similar stage of construction means the stage at which—
(i) Construction identifiable with a specific unit begins; and
(ii) Assembly of that unit comprising at least 50 metric tons (55.1 U.S. tons) or 1 percent of the estimated mass of all structural material, whichever is less, has been achieved.
(2) Unit constructed means a unit, the keel of which is laid or which is at a similar stage of construction.
(b) Subject to §108.515, each unit constructed before October 1, 1996, must meet the requirements of this subpart, except for the number, type, and arrangement of lifeboats (including survival capsules), lifeboat davits, winches, inflatable liferafts, liferaft launching equipment, and rescue boats.
(c)(1) If a District Commander determines that the overall safety of the persons on board a unit will not be significantly reduced, the District Commander may grant an exemption from compliance with a provision of this part to a specific unit for a specified geographic area within the boundaries of the Coast Guard District. This exemption may be limited to certain periods of the year.
(2) Requests for exemption under this paragraph must be in writing to the OCMI for transmission to the District Commander in the area in which the unit is in service or will be in service.
(3) If the exemption is granted by the District Commander, the OCMI will endorse the unit's Certificate of Inspection with a statement describing the exemption.
§ 108.515 Requirements for units built before October 1, 1996.
top
(a) Units which were constructed prior to October 1, 1996, must—
(1) By October 1, 1997, have either—
(i) Lifeboats and liferafts that meet §108.525; or
(ii) Totally enclosed fire-protected lifeboats of sufficient capacity to accommodate 100 percent of the persons permitted on board, plus additional totally enclosed lifeboats or davit-launched liferafts of sufficient capacity to accommodate 100 percent of the persons permitted on board the unit. The following exceptions apply:
(A) An open lifeboat may be used instead of davit-launched liferafts as long as it is in good working order. An open lifeboat requiring extensive repairs must be replaced with either a totally enclosed fire-protected lifeboat, or davit-launched liferafts.
(B) A submersible unit constructed before January 3, 1979, may continue to use the lifesaving arrangements described on the units Certificate of Inspection in effect on October 1, 1996.
(2) By October 1, 1997, fit retro-reflective material on all floating appliances, lifejackets, and immersion suits.
(3) Except for the requirements in paragraphs (a)(1) and (a)(2) of this section, units may retain the arrangement of lifesaving appliances previously required and approved for the unit, as long as the arrangement or appliance is maintained in good condition to the satisfaction of the OCMI.
(b) When any lifesaving appliance or arrangement on a unit subject to this part is replaced, or when the unit undergoes repairs, alterations or modifications of a major character involving replacement of, or any addition to, the existing lifesaving appliances or arrangements, each new lifesaving appliance and arrangement must meet the requirements of this part, unless the OCMI determines that the unit cannot accommodate the new appliance or arrangement, except that—
(1) A survival craft is not required to meet the requirements of this part if it is replaced without replacing its davit and winch; and
(2) A davit and its winch are not required to meet the requirements of this part if one or both are replaced without replacing the survival craft.
§ 108.520 Type of survival craft.
top
(a) Each lifeboat must be a fire-protected lifeboat approved under approval series 160.135. A lifeboat of aluminum construction in the hull or canopy must be protected in its stowage position by a water spray system meeting the requirements of part 34, subpart 34.25 of this chapter.
(b) Each inflatable liferaft must be approved under approval series 160.151. Each rigid liferaft must be approved under approval series 160.118. Each liferaft must have a capacity of six persons or more.
§ 108.525 Survival craft number and arrangement.
top
(a) Each unit must carry the following:
(1) Lifeboats installed in at least two widely separated locations on different sides or ends of the unit. The arrangement of the lifeboats must provide sufficient capacity to accommodate the total number of persons permitted on board if—
(i) All the lifeboats in any one location are lost or rendered unusable; or
(ii) All the lifeboats on any one side or end of the unit are lost or rendered unusable.
(2) Liferafts arranged for float-free launching and having an aggregate capacity that will accommodate the total number of persons permitted on board.
(b) In the case of a self-elevating unit where, due to its size or configuration, lifeboats can not be located in the widely separated locations required under paragraph (a)(1) of this section, the OCMI may accept the following number and arrangement of survival craft:
(1) Lifeboats with an aggregate capacity to accommodate the total number of persons permitted on board.
(2) Liferafts served by launching appliances or marine evacuation systems of an aggregate capacity to accommodate the total number of persons permitted on board. These liferafts may be the float-free liferafts under paragraph (a)(2) of this section, or liferafts in addition to the float-free liferafts.
§ 108.530 Stowage of survival craft.
top
(a) General. Each survival craft required to be served by a launching appliance or marine evacuation system must be stowed as follows:
(1) Each survival craft must be stowed as close to the accommodation and service spaces as possible.
(2) Each survival craft must be stowed in a way that neither the survival craft nor its stowage arrangements will interfere with the embarkation and operation of any other survival craft or rescue boat at any other launching station.
(3) Each survival craft must be stowed as near the water surface as is safe and practicable.
(4) Each survival craft must be stowed where the survival craft, in the embarkation position, is above the waterline with the unit—
(i) In the fully loaded condition; and
(ii) Listed up to 20 degrees either way, or to the angle where the unit's weatherdeck edge becomes submerged, whichever is less.
(5) Each survival craft must be sufficiently ready for use so that two crew members can complete preparations for embarkation and launching in less than 5 minutes.
(6) Each survival craft must be fully equipped as required under this subpart.
(7) Each survival craft must be in a secure and sheltered position and protected from damage by fire and explosion, as far as practicable.
(8) Each survival craft must not require lifting from its stowed position in order to launch, except that a davit-launched liferaft may be lifted by a manually powered winch from its stowed position to its embarkation position.
(b) Additional lifeboat-specific stowage requirements. In addition to meeting the requirements of paragraph (a) of this section, each lifeboat must be stowed as follows:
(1) The unit must be arranged so each lifeboat, in its stowed position, is protected from damage by heavy seas.
(2) Each lifeboat must be stowed attached to its launching appliance.
(3) Each lifeboat must be provided a means for recharging the lifeboat batteries from the unit's power supply at a supply voltage not exceeding 50 volts.
(c) Additional liferaft-specific stowage requirements. In addition to meeting the requirements of paragraph (a) of this section, each liferaft must be stowed as follows:
(1) Each liferaft must be stowed to permit manual release from its securing arrangements.
(2) Each liferaft must be stowed at a height above the waterline in the lightest seagoing condition, not greater than the maximum stowage height indicated on the liferaft. Each liferaft without an indicated maximum stowage height must be stowed not more than 18 meters (59 feet) above the waterline in the unit's lightest seagoing condition.
(3) Each liferaft must be arranged to permit it to drop into the water from the deck on which it is stowed. A liferaft stowage arrangement meets this requirement if it—
(i) Is outboard of the rail or bulwark;
(ii) Is on stanchions or on a platform adjacent to the rail or bulwark; or
(iii) Has a gate or other suitable opening to allow the liferaft to be pushed directly overboard.
(4) Each davit-launched liferaft must be stowed within reach of its lifting hook, unless some means of transfer is provided that is not rendered inoperable—
(i) Within the list limits specified in paragraph (a)(4)(ii) of this section;
(ii) By unit motion; or
(iii) By power failure.
(5) Each rigid container for an inflatable liferaft to be launched by a launching appliance must be secured in a way that the container or parts of it are prevented from falling into the water during and after inflation and launching of the contained liferaft.
(6) Each liferaft must have a painter system providing a connection between the unit and the liferaft.
(7) Each liferaft or group of liferafts must be arranged for float-free launching. The arrangement must ensure that the liferaft or liferafts when released and inflated, are not dragged under by the sinking unit. A hydrostatic release unit used in a float-free arrangement must be approved under approval series 160.162.
§ 108.540 Survival craft muster and embarkation arrangements.
top
(a) Each muster station must have sufficient space to accommodate all persons assigned to muster at that station. One or more muster stations must be close to each embarkation station.
(b) Each muster station and embarkation station must be readily accessible from accommodation and work areas.
(c) Each lifeboat must be arranged to be boarded and launched directly from the stowed position.
(d) Each lifeboat must be arranged to be boarded by its full complement of persons within 3 minutes from the time the instruction to board is given.
(e) Each davit-launched and free-fall survival craft muster station and embarkation station for a survival craft which is boarded before it is launched must be arranged to enable stretcher cases to be placed in the survival craft.
(f) Means must be provided for bringing each davit-launched survival craft against the side of the unit and holding it alongside to allow persons to be—
(1) Safely embarked in the case of a survival craft intended to be boarded over the edge of the deck; and
(2) Safely disembarked after a drill in the case of a survival craft not intended to be moved to the stowed position with a full complement of persons on board. (continued)